5-64
L3-02
Stall
Prevention
Level
During
Acceleration
This function is enabled when
L3-01 is "1" or "2".
Drive rated current is 100%.
Decrease the set value if
stalling or excessive current
occurs with factory setting.
0
to
200
150% No A A A No No 490H
StallP
Accel Lvl
L3-03
Stall
Prevention
Limit
During
Acceleration
Sets the lower limit for stall
prevention during acceleration,
as a percentage of the Drive's
rated current, when operation is
in the frequency range above
E1-06 (constant power region).
0
to
100
50% No A A A No No 491H
StallP CHP
Lvl
L3-04
Stall
Prevention
Selection
During
Deceleration
When using a braking resistor,
use setting "0". Setting "3" is
used in specific applications.
0: Disabled - The Drive
decelerates at the active
deceleration rate. If the load
is too large or the
deceleration time is too
short, an OV fault may
occur.
1: General Purpose - The Drive
decelerates at the active
deceleration rate, but if the
main circuit DC bus voltage
reaches the stall prevention
level (380/760Vdc),
deceleration will stop.
Deceleration will continue
once the DC bus level drops
below the stall prevention
level.
2: Intelligent - The active
deceleration rate is ignored
and the Drive decelerates as
fast as possible w/o hitting
OV fault level.
Range: C1-02 / 10.
3: Stall Prevention w/ Braking
Resistor - Stall prevention
during deceleration is
enabled in coordination with
dynamic braking.
0 to 3
*
1 No Q Q Q Q Q 492H
StallP
Decel Sel
Parameter
Number
Name
Description
Setting
Range
Factory
Setting
Change
during
Operation
Control Methods
MODBUS
Register
Display
V/f
V/f
with
PG
Open
Loop
Vector
1
Flux
Vector
Open
Loop
Vector
2
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com