EasyManuals Logo

YASKAWA G7 Series User Manual

YASKAWA G7 Series
456 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #183 background imageLoading...
Page #183 background image
User Parameter Tables
5-71
Torque Limits: L7
User parameters for torque limits are shown in the following table.
Parameter
Number
Name Description
Setting
Range
Factory
Setting
Change
during
Operation
Control Methods
MODBUS
Register
V/f
V/f
with
PG
Open
Loop
Vector
1
Flux
Vector
Open
Loop
Vector
2
L7-01
Forward
Torque
Limit
Sets the torque limit value as a
percentage of the motor rated torque.
Four individual quadrants can be set.
0
to
300
200% No No No A A A 4A7H
Torq Limit
Fwd
L7-02
Reverse
Torque
Limit
0
to
300
200% No No No A A A 4A8H
Torq Limit
Rev
L7-03
Forward
Regenerative
Torque
Limit
0
to
300
200% No No No A A A 4A9H
Torq Lmt
Fwd Rgn
L7-04
Reverse
Regenerative
Torque
Limit
0
to
300
200% No No No A A A 4AAH
Torq Lmt
Rev Rgn
L7-06
Torque
Limit
Integral
Time
Constant
Sets the torque limit value as a per-
centage of the motor rated torque. Four
individual quadrants can be set.
5
to
10000
200ms No No No A No No 4ACH
Torq Det 2
Time
L7-07
Torque
Limit
Control
Method
Selection
During
Accel/
Decel
Selects the method of torque limit
controls during accel/decel
0: Proportional Controls (uses integral
controls at fixed speeds).
1: Integral Controls
Adjustment is not normally
required. With applications that
require torque limits during
accel/decel, integral controls (setting
value = 1) are used when torque
controls take precedence. When
torque limit is applied to the motor,
accel/decel time may increase and
motor speed may not run at the
indicated speed reference.
0 to 1 0 No No No A No No 4C9H
Torq Lmt
Sel
Output torque
Positive torque
Reverse
Negative torque
No. of
motor
rotations
Regenerative
state
Regenerative
state
Forward
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the YASKAWA G7 Series and is the answer not in the manual?

YASKAWA G7 Series Specifications

General IconGeneral
SeriesG7
Frequency50/60 Hz
Output VoltageMatches Input Voltage
Control MethodV/f Control
Overload Capacity150% for 60 seconds
Protection FeaturesOvercurrent, Overvoltage, Undervoltage, Overheating, Short Circuit
CommunicationRS-485, Modbus, DeviceNet, Profibus, Ethernet
SafetySafe Torque Off (STO)
Operating Temperature-10°C to 50°C
Humidity5% to 95% (non-condensing)
Cooling MethodFan Cooled
Enclosure RatingIP20
Storage Temperature-20°C to 65°C

Related product manuals