User Parameter Tables
5-85
* 1. Set T1-02 and T1-04 when 2 is set for T1-01. Only set value 2 is possible for V/f control or V/f control with PG.
* 2. Setting value for 208-240Vac. Double the value when working with 380-480Vac drives.
* 3. Factory settings will vary based on drive capacity (values given here are for 208-240Vac, 0.4kW).
* 4. Setting range is 10% to 200% of the drive's rated output current (values given here are for 208-240Vac, 0.4kW).
* 5. The upper setting limit will be 150.0Hz when C6-01 is set to 0.
* 6. Use this type of auto-tuning only if having problems with precision when tuning.
T1-07
Motor Base
Speed
Sets the base speed of the
motor in revolutions per
minute (RPM).
0
to
24000
1750
min
1
No No No Yes Yes Yes 707H
Rated Speed
T1-08
Number of
PG Pulses
Sets the number of pulses per
revolution (PPR) for the
encoder (pulse generator)
being used without any
multiplication factor.
0
to
60000
600 No No Yes No Yes No 708H
PG Pulses/
Rev
Parameter
Number
Name
Description
Setting
Range
Factory
Setting
Change
during
Operation
Control Methods
MODBUS
Register
Display
V/f
V/f
with
PG
Open
Loop
Vector
1
Flux
Vector
Open
Loop
Vector
2
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the YASKAWA G7 Series and is the answer not in the manual?

YASKAWA G7 Series Specifications

General IconGeneral
SeriesG7
Frequency50/60 Hz
Output VoltageMatches Input Voltage
Control MethodV/f Control
Overload Capacity150% for 60 seconds
Protection FeaturesOvercurrent, Overvoltage, Undervoltage, Overheating, Short Circuit
CommunicationRS-485, Modbus, DeviceNet, Profibus, Ethernet
SafetySafe Torque Off (STO)
Operating Temperature-10°C to 50°C
Humidity5% to 95% (non-condensing)
Cooling MethodFan Cooled
Enclosure RatingIP20
Storage Temperature-20°C to 65°C