User Parameter Tables
5-99
208-240Vac and 380-480Vac Drives of 2.2 to 45 kW
Table 5.4 V/F Pattern for Drive Capacity G7U22P2 - 2045 for 208-240V Class
Parameter
No.
Name Unit Factory Setting
E1-03 V/F Pattern Selection 0 1 2 3 4 5 6 7
E1-04 Max. Output Frequency Hz 50.0 60.0 60.0 72.0 50.0 50.0 60.0 60.0
E1-05 Max. Output Voltage V 230.0 230.0 230.0 230.0 230.0 230.0 230.0 230.0
E1-06 Base Frequency Hz 50.0 60.0 50.0 60.0 50.0 50.0 60.0 60.0
E1-07 Mid. Output Frequency V 2.5 3.0 3.0 3.0 25.0 25.0 30.0 30.0
E1-08 Mid. Output Voltage V 16.1 16.1 16.1 16.1 40.2 57.5 40.2 57.5
E1-09 Min. Output Frequency Hz 1.3 1.5 1.5 1.5 1.3 1.3 1.5 1.5
E1-10 Min. Output Voltage V 8.0 8.0 8.0 8.0 6.9 8.0 6.9 8.0
1. The setting shown are for 208-240Vac Drives. The values will double for 380-480Vac Drives.
2. These default values are for V/F or V/F with PG control methods (A1-02 = 0 or 1)
Table 5.4 V/F Pattern for Drive Capacity G7U22P2 - 2045 for 208-240V Class (continued)
Parameter
No.
Name Unit Factory Setting
E1-03 V/F Pattern Selection 8 9 A B C D E
F &
FF
E1-04 Max. Output Frequency Hz 50.0 50.0 60.0 60.0 90.0 120.0 180.0 60.0
E1-05 Max. Output Voltage V 230.0 230.0 230.0 230.0 230.0 230.0 230.0 230.0
E1-06 Base Frequency Hz 50.0 50.0 60.0 60.0 60.0 60.0 60.0 60.0
E1-07 Mid. Output Frequency V 2.5 2.5 3.0 3.0 3.0 3.0 3.0 3.0
E1-08 Mid. Output Voltage V 20.7 26.4 20.7 26.4 16.1 16.1 16.1 16.1
E1-09 Min. Output Frequency Hz 1.3 1.3 1.5 1.5 1.5 1.5 1.5 1.5
E1-10 Min. Output Voltage V 10.3 12.6 10.3 14.9 8.0 8.0 8.0 8.0
1. For 400V class units, the voltage values are twice that of 200V class units.
2. These default values are for V/F or V/F with PG control methods (A1-02 = 0 or 1)
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the YASKAWA G7 Series and is the answer not in the manual?

YASKAWA G7 Series Specifications

General IconGeneral
SeriesG7
Frequency50/60 Hz
Output VoltageMatches Input Voltage
Control MethodV/f Control
Overload Capacity150% for 60 seconds
Protection FeaturesOvercurrent, Overvoltage, Undervoltage, Overheating, Short Circuit
CommunicationRS-485, Modbus, DeviceNet, Profibus, Ethernet
SafetySafe Torque Off (STO)
Operating Temperature-10°C to 50°C
Humidity5% to 95% (non-condensing)
Cooling MethodFan Cooled
Enclosure RatingIP20
Storage Temperature-20°C to 65°C