6-132
Adjusting ASR Integral Time 1 (C5-02)
This parameter sets the speed control (ASR) integral time.
Lengthening the integral time lowers the responsiveness, and weakens the resistance to external influences.
Oscillation will occur if this setting is too short. The following diagram shows the type of changes that can
occur in the response when the ASR integral time is changed.
Fig 6.69 Responsiveness for Integral Time
Different Gain Settings for Low-speed and High-speed
Switch between low-speed and high-speed gain when oscillation occurs because of resonance with the
mechanical system at low speed or high speed. The proportional gain P and integral time I can be switched
according to the motor speed, as shown below.
Fig 6.70 Low-speed and High-speed Gain Settings
Setting the Gain Switching Frequency (C5-07)
Set the switching frequency to about 80% of the motor operating frequency or the frequency at which oscilla-
tion occurs.
Low-speed Gain Adjustments (C5-03, C5-04)
Connect the actual load and adjust these parameters at zero-speed. Increase C5-03 (ASR proportional gain 2)
until there is no oscillation. Decrease C5-04 (ASR integral time 2) until there is no oscillation.
Motor speed
Time
Short integral time
Long integral time
P, I
Motor speed (Hz)
P = C5-01
I = C5-02
P = C5-03
I = C5-04 (Low speed)
C5-07
If C5-07 is set to 0, P = C5-01 and I = C5-02.
0
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the YASKAWA G7 Series and is the answer not in the manual?

YASKAWA G7 Series Specifications

General IconGeneral
SeriesG7
Frequency50/60 Hz
Output VoltageMatches Input Voltage
Control MethodV/f Control
Overload Capacity150% for 60 seconds
Protection FeaturesOvercurrent, Overvoltage, Undervoltage, Overheating, Short Circuit
CommunicationRS-485, Modbus, DeviceNet, Profibus, Ethernet
SafetySafe Torque Off (STO)
Operating Temperature-10°C to 50°C
Humidity5% to 95% (non-condensing)
Cooling MethodFan Cooled
Enclosure RatingIP20
Storage Temperature-20°C to 65°C

Related product manuals