EasyManuals Logo

YASKAWA G7 Series User Manual

YASKAWA G7 Series
456 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #41 background imageLoading...
Page #41 background image
Wiring Main Circuit Terminals
2-9
G7U4030
R/L1, S/L2, T/L3, , 1, U/T1, V/T2,
W/T3, R1/L11, S1/L21, T1/L31
M8
79.2 to 88
(9.0 to 10.0)
8 to 1/0
(8 to 60)
2
(38)
Power cables,
e.g., 600 V
vinyl power
cables
3
M6
35.2 to 44
(4.0 to 5.0)
(8 to 4)
8 to 22
Application
Dependent
M8
79.2 to 88
(9.0 to 10.0)
*3 *3
G7U4037
R/L1, S/L2, T/L3, , 1, U/T1, V/T2,
W/T3, R1/L11, S1/L21, T1/L31
M8
79.2 to 88
(9.0 to 10.0)
2 to 1/0
(30 to 60)
2
(38)
G7U4045
R/L1, S/L2, T/L3, , 1, U/T1, V/T2,
W/T3, R1/L11, S1/L21, T1/L31
M8
79.2 to 88
(9.0 to 10.0)
8 to 1/0
(8 to 60)
1
(50)
3
M6
35.2 to 44
(4.0 to 5.0)
8 to 4
(8 to 22)
Application
Dependent
M8
79.2 to 88
(9.0 to 10.0)
*3 *3
G7U4055
R/L1, S/L2, T/L3, , 1, U/T1, V/T2,
W/T3, R1/L11, S1/L21, T1/L31
M10
154.8 to 197.5
(17.6 to 22.5)
N/A
1/0
(50)
3
M8
78 to 95
(8.8 to 10.8)
Application
Dependent
M10
154.8 to 197.5
(17.6 to 22.5)
2
(38)
r/ 1, 200/
2
200, 400/
2
400
M4
11.4 to 12.3
(1.3 to 1.4)
16
(1.25)
G7U4075
R/L1, S/L2, T/L3, , 1, U/T1, V/T2,
W/T3, R1/L11, S1/L21, T1/L31
M10
154.8 to 197.5
(17.6 to 22.5)
4/0
(100)
3
M8
78 to 95
(8.8 to 10.8)
Application
Dependent
M10
154.8 to 197.5
(17.6 to 22.5)
1
(50)
r/ 1, 200/
2
200, 400/
2
400
M4
11.4 to 12.3
(1.3 to 1.4)
16
(1.25)
G7U4090
R/L1, S/L2, T/L3, , 1, U/T1, V/T2,
W/T3, R1/L11, S1/L21, T1/L33
M10
154.8 to 197.5
(17.6 to 22.5)
1/0 × 2P
(50 × 2P)
3
M8
78 to 95
(8.8 to 10.8)
Application
Dependent
M12
154.8 to 197.5
(17.6 to 22.5)
2/0
(60)
r/ 1, 200/
2
200, 400/
2
400
M4
11.4 to 12.3
(1.3 to 1.4)
16
(1.25)
G7U4110
R/L1, S/L2, T/L3, , 1, U/T1, V/T2,
W/T3, R1/L11, S1/L21, T1/L33
M10
154.8 to 197.5
(17.6 to 22.5)
3/0 × 2P
(80 × 2P)
3
M8
78 to 95
(8.8 to 10.8)
Application
Dependent
M12
154.8 to 197.5
(17.6 to 22.5)
4/0
(100)
r/ 1, 200/
2
200, 400/
2
400
M4
11.4 to 12.3
(1.3 to 1.4)
16
(1.25)
G7U4132
R/L1, S/L2, T/L3, , 1, U/T1, V/T2,
W/T3, R1/L11, S1/L21, T1/L31
M12
276 to 345
(31.4 to 39.2)
3/0 × 2P
(80 × 2P)
3
M8
78 to 95
(8.8 to 10.8)
Application
Dependent
M12
276 to 345
(31.4 to 39.2)
1/0 × 2P
(50 × 2P)
r/ 1, 200/
2
200, 400/
2
400
M4
11.4 to 12.3
(1.3 to 1.4)
16
(1.25)
Drive Model
CIMR-
Terminal Symbol
Terminal
Screws
Tightening
Torque
(N•m)
Possible Wire
Sizes
mm
2
(AWG)
Recommended
Wire Size
mm
2
(AWG)
Wire Type
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the YASKAWA G7 Series and is the answer not in the manual?

YASKAWA G7 Series Specifications

General IconGeneral
SeriesG7
Frequency50/60 Hz
Output VoltageMatches Input Voltage
Control MethodV/f Control
Overload Capacity150% for 60 seconds
Protection FeaturesOvercurrent, Overvoltage, Undervoltage, Overheating, Short Circuit
CommunicationRS-485, Modbus, DeviceNet, Profibus, Ethernet
SafetySafe Torque Off (STO)
Operating Temperature-10°C to 50°C
Humidity5% to 95% (non-condensing)
Cooling MethodFan Cooled
Enclosure RatingIP20
Storage Temperature-20°C to 65°C