10-14
380-480
V class
40P4 480 5 16 to 660 CR6L-20/UL FUJI
600 V
20 A
26
40P7 480 10 19 to 660 CR6L-20/UL FUJI
600 V
20 A
26
41P5 480 10 46 to 660 CR6L-30/UL FUJI
600 V
30 A
59
42P2 480 15 78 to 660 CR6L-50/UL FUJI
600 V
50 A
317
43P7 480 20 110 to 660 CR6L-50/UL FUJI
600 V
50 A
317
44P0 480 30 220 to 660 CR6L-50/UL FUJI
600 V
50 A
317
45P5 480 40 240 to 900 CR6L-50/UL FUJI
600 V
50 A
317
47P5 480 50 320 to 900 CR6L-75/UL FUJI
600 V
75 A
564
4011 480 50 1000 to 1800 CR6L-100/UL FUJI
600 V
100 A
1022
4015 480 60 1500 to 4100 CR6L-150/UL FUJI
600 V
150 A
3070
4018 480 70 530 to 5800 CR6L-150/UL FUJI
600 V
150 A
3070
4022 480 90 1130 to 5800 CR6L-150/UL FUJI
600 V
150 A
3070
4030 480 110 1700 to 5800 CR6L-150/UL FUJI
600 V
150 A
3070
4037 480 140 2000 to 13000 CR6L-200/UL FUJI
600 V
200 A
5200
4045 480 160 3000 to 13000 CR6L-200/UL FUJI
600 V
200 A
5200
4055 480 220 6800 to 55000 CR6L-300/UL FUJI
600 V
300 A
17700
4075 480 280 9000 to 55000 CR6L-300/UL FUJI
600 V
300 A
17700
4090 480 330 12000 to 23000 A70P400-4 FERRAZ
700 V
400 A
19000
4110 480 400 18000 to 64000 A70P450-4 FERRAZ
700 V
450 A
24000
4132 480 450 28000 to 250000 A70P600-4 FERRAZ
700 V
600 A
43000
4160 480 540 40000 to 250000 A70P700-4 FERRAZ
700 V
700 A
59000
4185 480 620 43000 to 400000 A70P900-4 FERRAZ
700 V
900 A
97000
4220 480 750 63000 to 400000 A70P900-4 FERRAZ
700 V
900 A
97000
4300 480 1000 94000 to 920000 A70P1000-4 FERRAZ
700 V
1000 A
120000
Table 10.2 Selection Requirements for Input Fuses with Examples
Voltage
Class
Drive Model
Number
CIMR-G7U
Selection Requirements Input Fuse (Examples)
Voltage
(V)
Current
(A)
Fusing I
2
t
(A
2
sec)
Model Number Manufacturer Ratings
Fusing
I
2
t
(A
2
sec)
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the YASKAWA G7 Series and is the answer not in the manual?

YASKAWA G7 Series Specifications

General IconGeneral
SeriesG7
Frequency50/60 Hz
Output VoltageMatches Input Voltage
Control MethodV/f Control
Overload Capacity150% for 60 seconds
Protection FeaturesOvercurrent, Overvoltage, Undervoltage, Overheating, Short Circuit
CommunicationRS-485, Modbus, DeviceNet, Profibus, Ethernet
SafetySafe Torque Off (STO)
Operating Temperature-10°C to 50°C
Humidity5% to 95% (non-condensing)
Cooling MethodFan Cooled
Enclosure RatingIP20
Storage Temperature-20°C to 65°C