10-16
Fig 10.7 Installation Method for Filter and Drive (CIMR-G7U2022 to 2110, 4022 to 4300)
Table 10.3 EMC Noise Filters
Voltage
Class
Drive Model
Number
CIMR-G7U
Noise Filter (Made by Schaffner)
Model Number Rated Current (A) Weight (kg) Dimensions
200-
240 V
class
20P4
FS 5972-10-07 10 1.1 141 x 330 x 46
20P7
21P5 FS 5972-18-07 18 1.3 141 x 330 x 46
22P2
FS 5972-35-07 35 1.4 141 x 330 x 46
23P7
25P5
FS 5972-60-07 60 3 206 x 355 x 60
27P5
2011
FS 5972-100-07 100 4.9 236 x 408 x 802015
2018
2022 FS 5972-120-35 120 4.3 90 x 366 x 180
2030
FS 5972-180-40 180 6 120 x 451 x 170
2037
2045
FS 5972-300-37 300 11 130 x 610 x 240
2055
2075 FS 5972-300-37 360 11 130 x 610 x 240
2090
FS 5972-300-37 450 11 130 x 610 x 240
2110
PE
IM
L1L2L3
L1L2L3 T1 T3T2
Remove the paint on the ground side.
Inputs
Filter
Outputs
Drive
Wiring length:
40 cm max.
Metallic plate
Wiring length: 20 m max.
Remove the paint on the ground side.
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the YASKAWA G7 Series and is the answer not in the manual?

YASKAWA G7 Series Specifications

General IconGeneral
SeriesG7
Frequency50/60 Hz
Output VoltageMatches Input Voltage
Control MethodV/f Control
Overload Capacity150% for 60 seconds
Protection FeaturesOvercurrent, Overvoltage, Undervoltage, Overheating, Short Circuit
CommunicationRS-485, Modbus, DeviceNet, Profibus, Ethernet
SafetySafe Torque Off (STO)
Operating Temperature-10°C to 50°C
Humidity5% to 95% (non-condensing)
Cooling MethodFan Cooled
Enclosure RatingIP20
Storage Temperature-20°C to 65°C

Related product manuals