1.21 Defaults by Drive Model and Duty Rating ND/HD
148 YASKAWA TOEPYAIGA8002B GA800 Drive Programming
No. Name Unit Default
- Drive Model - 4371 4414 4477 4568
C6-01
Normal /
Heavy Duty
Selection
-
HD ND HD ND HD ND HD ND
0 1 0 1 0 1 0 1
o2-04
Drive Model
(KVA)
Selection
Hex. A9 AA AC AD
E2-11
(E4-11, E5-
02)
Motor Rated
Power
HP (kW)
200
(160)
250
(200)
250
(200)
300
(220)
300
(220)
335
(250)
335
(250)
400
(315)
b3-04
V/f Gain
during Speed
Search
% 60 60 60 60 60 60 60 60
b3-06
Speed
Estimation
Current Level
1
- 0.7 0.7 0.7 0.7 0.7 0.7 0.7 0.7
b3-08
Speed
Estimation
ACR P Gain
- 0.8 0.8 0.8 0.8 0.8 0.8 0.8 0.8
b3-26
Direction
Determination
Level
- 1000 1000 1000 1000 1000 1000 1000 1000
b8-03
Energy Saving
Filter Time
s 2.00 2.00 2.00 2.00 2.00 2.00 2.00 2.00
b8-04
Energy Saving
Coefficient
Value
- 30.13 30.57 30.57 27.13 27.13 21.76 21.76 21.76
C5-17
(C5-37)
Motor Inertia kgm
2
3.30 3.60 3.60 4.10 4.10 6.50 6.50 11.00
C6-02
Carrier
Frequency
Selection
- 1 7 1 7 1 7 1 7
E2-01
(E4-01)
Motor Rated
Current (FLA)
A 270 310 310 370 370 500 500 500
E2-02
(E4-02)
Motor Rated
Slip
Hz 1.35 1.3 1.3 1.3 1.3 1.25 1.25 1.25
E2-03
(E4-03)
Motor No-
Load Current
A 70 81 81 96 96 130 130 130
E2-05
(E4-05)
Motor Line-to-
Line
Resistance
Ω 0.029 0.025 0.025 0.02 0.02 0.014 0.014 0.014
E2-06
(E4-06)
Motor
Leakage
Inductance
% 20 20 20 20 20 20 20 20
E2-10
(E4-10)
Motor Iron
Loss
W 2850 3200 3200 3700 3700 4700 4700 4700
E5-01
PM Motor
Code Selection
- FFFF FFFF FFFF FFFF FFFF FFFF FFFF FFFF
L2-02
Power Loss
Ride Through
Time
s 2 2 2 2 2 2 2 2
L2-03
Minimum
Baseblock
Time
s 1.8 1.9 1.9 2 2 2.1 2.1 2.1
L2-04
Powerloss V/f
Recovery
Ramp Time
s 1 1 1.8 1.8 1.8 2 2 2
L2-05
Undervoltage
Detection Lvl
(Uv1)
- 380 380 380 380 380 380 380 380
L3-24
Motor Accel
Time for
Inertia Cal
s 0.777 0.864 0.864 0.91 0.91 1.392 1.392 1.392
L8-02
Overheat
Alarm Level
°C 125 125 125 125 110 110 125 115