1.22 Parameters Changed by PM Motor Code Selection
156 YASKAWA TOEPYAIGA8002B GA800 Drive Programming
No. Name Unit Motor Code (setting value of E5-01)
E1-09
Minimum Output
Frequency
Hz 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6
C5-17 Motor Inertia kgm
2
0.0017 0.0023 0.0043 0.0083 0.0136 0.017 0.027 0.046
L3-24
*1
Motor Accel Time @
Rated Torque
s 0.098 0.071 0.066 0.087 0.085 0.072 0.084 0.096
n5-02
Motor Inertia
Acceleration Time
s 0.098 0.071 0.066 0.087 0.085 0.072 0.084 0.096
n8-49 Heavy Load Id Current % -6.6 -10.9 -13.5 -9.0 -9.5 -10.1 -6.0 -9.3
*1 The default setting changes when the setting for o2-04 [Drive Model Selection] changes.
Table 1.12 SSR1 Series Motor Code Setting for Specification of 200 V at 1450 min
-1
(r/min)
No. Name Unit Motor Code (setting value of E5-01)
E5-01
PM Motor Code Selection - 130E 130F 1310 1312 1313 1314 1315
Voltage Class V 200 200 200 200 200 200 200
Capacity kW 15 18 22 30 37 45 55
Motor Rotation Speed min
-1
1450 1450 1450 1450 1450 1450 1450
E5-02 PM Motor Rated Power kW 15.00 18.50 22.00 30.00 37.00 45.00 55.00
E5-03
PM Motor Rated Current
(FLA)
A 55.5 65.6 75.1 105.2 126.0 153.1 186.5
E5-04 PM Motor Pole Count - 6 6 6 6 6 6 6
E5-05
PM Motor Resistance
(ohms/phase)
Ω 0.075 0.057 0.041 0.034 0.023 0.015 0.012
E5-06
PM d-axis Inductance (mH/
phase)
mH 3.29 2.53 1.98 1.75 1.48 1.04 0.87
E5-07
PM q-axis Inductance (mH/
phase)
mH 3.84 3.01 2.60 2.17 1.70 1.31 1.10
E5-09
PM Back-EMF Vpeak
(mV/(rad/s))
mVs/rad 311.2 300.9 327.7 354.2 369.6 351.6 374.7
E5-24
PM Back-EMF L-L Vrms
(mV/rpm)
mV/min
-1
0.0 0.0 0.0 0.0 0.0 0.0 0.0
E1-04
Maximum Output
Frequency
Hz 72.5 72.5 72.5 72.5 72.5 72.5 72.5
E1-05 Maximum Output Voltage V 190.0 190.0 190.0 190.0 190.0 190.0 190.0
E1-06 Base Frequency Hz 72.5 72.5 72.5 72.5 72.5 72.5 72.5
E1-09
Minimum Output
Frequency
Hz 3.6 3.6 3.6 3.6 3.6 3.6 3.6
C5-17 Motor Inertia kgm
2
0.055 0.064 0.116 0.140 0.259 0.312 0.42
L3-24
*1
Motor Accel Time @ Rated
Torque
s 0.085 0.080 0.122 0.108 0.161 0.160 0.175
n5-02
Motor Inertia Acceleration
Time
s 0.085 0.080 0.122 0.108 0.161 0.160 0.175
n8-49 Heavy Load Id Current % -10.7 -13.2 -15.7 -11.5 -7.0 -11.8 -10.2
*1 The default setting changes when the setting for o2-04 [Drive Model Selection] changes.
Table 1.13 SSR1 Series Motor Code Setting for Specification of 400 V at 1450 min
-1
(r/min)
No. Name Unit Motor Code (setting value of E5-01)
E5-01
PM Motor Code
Selection
- 1332 1333 1335 1336 1338 133A 133B 133D
Voltage Class V 400 400 400 400 400 400 400 400
Capacity kW 0.4 0.75 1.5 2.2 3.7 5.5 7.5 11
Motor Rotation Speed min
-1
1450 1450 1450 1450 1450 1450 1450 1450
E5-02 PM Motor Rated Power kW 0.4 0.75 1.5 2.2 3.7 5.5 7.5 11.0