Parameter List
1
1.22 Parameters Changed by PM Motor Code Selection
YASKAWA TOEPYAIGA8002B GA800 Drive Programming 161
No. Name Unit Motor Code (setting value of E5-01)
E1-04 Maximum Output Frequency Hz 57.5 57.5 57.5 57.5 57.5 57.5
E1-05 Maximum Output Voltage V 380.0 380.0 380.0 380.0 380.0 380.0
E1-06 Base Frequency Hz 57.5 57.5 57.5 57.5 57.5 57.5
E1-09 Minimum Output Frequency Hz 2.9 2.9 2.9 2.9 2.9 2.9
C5-17 Motor Inertia kgm
2
0.064 0.116 0.140 0.259 0.312 0.418
L3-24
*1
Motor Accel Time @ Rated
Torque
s 0.062 0.091 0.092 0.125 0.122 0.135
n5-02
Motor Inertia Acceleration
Time
s 0.062 0.091 0.092 0.125 0.122 0.135
n8-49 Heavy Load Id Current % -14.9 -17.9 -15.9 -17.7 -20.1 -13.8
*1 The default setting changes when the setting for o2-04 [Drive Model Selection] changes.
Table 1.20 SSR1 Series Motor Code Setting for Specification of 400 V at 1150 min
-1
(r/min)
No. Name Unit Motor Code (setting value of E5-01)
E5-01
PM Motor Code Selection - 1445 1446 1447 1448
Voltage Class V 400 400 400 400
Capacity kW 55 75 90 110
Motor Rotation Speed min
-1
1150 1150 1150 1150
E5-02 PM Motor Rated Power kW 55.00 75.00 90.00 110.00
E5-03 PM Motor Rated Current (FLA) A 92.0 127.1 150.5 185.4
E5-04 PM Motor Pole Count - 6 6 6 6
E5-05
PM Motor Resistance (ohms/
phase)
Ω 0.051 0.033 0.027 0.015
E5-06
PM d-axis Inductance (mH/
phase)
mH 3.96 3.03 2.60 1.89
E5-07
PM q-axis Inductance (mH/
phase)
mH 5.00 5.14 3.28 2.33
E5-09
PM Back-EMF Vpeak (mV/(rad/
s))
mVs/rad 854.0 823.1 853.4 829.2
E5-24
PM Back-EMF L-L Vrms (mV/
rpm)
mV/min
-1
0.0 0.0 0.0 0.0
E1-04 Maximum Output Frequency Hz 57.5 57.5 57.5 57.5
E1-05 Maximum Output Voltage V 380.0 380.0 380.0 380.0
E1-06 Base Frequency Hz 57.5 57.5 57.5 57.5
E1-09 Minimum Output Frequency Hz 2.9 2.9 2.9 2.9
C5-17 Motor Inertia kgm
2
0.56 0.83 0.96 1.61
L3-24
*1
Motor Accel Time @ Rated
Torque
s 0.147 0.161 0.154 0.212
n5-02 Motor Inertia Acceleration Time s 0.147 0.161 0.154 0.212
n8-49 Heavy Load Id Current % -12.5 -28.8 -13.3 -11.6
*1 The default setting changes when the setting for o2-04 [Drive Model Selection] changes.