EasyManua.ls Logo

YASKAWA GA800

YASKAWA GA800
644 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Parameter Details
2
2.3 b: Application
YASKAWA TOEPYAIGA8002B GA800 Drive Programming 195
Figure 2.8 Example of Setting the Frequency Reference with a Voltage Signal to Terminal A1
Note:
You can also use this diagram to wire terminals A2 and A3.
Current Input
Refer to Table 2.19 to use a current signal input to one of the MFAI terminals.
Table 2.19 Frequency Reference Current Input
Terminal Signal Level
Parameter Settings
Note
Signal Level
Selection
Function Selection Gain Bias
A1 4 mA to 20 mA H3-01 = 2 H3-02 = 0
[Frequency Bias]
H3-03 H3-04 Set DIP switch S1-1 to I for
current input.
0 - 20 mA H3-01 = 3
A2 4 mA to 20 mA H3-09 = 2 H3-10 = 0
[Frequency Bias]
H3-11 H3-12 Set DIP switch S1-2 to I for
current input.
0 - 20 mA H3-09 = 3
A3 4 mA to 20 mA H3-05 = 2 H3-06 = 0
[Frequency Bias]
H3-07 H3-08 Set DIP switch S1-3 to I for
current input.
Set DIP switch S4 to AI for
analog input.
0 - 20 mA H3-05 = 3
Figure 2.9 Example of Setting the Frequency Reference with a Current Signal to Terminal A2
Note:
You can also use this diagram to wire terminals A1 and A3.
Changing between Master and Auxiliary Frequency References
Use the multi-step speed reference function to change the frequency reference input between terminals A1, A2, and
A3.
2 : Memobus/Modbus Communications