EasyManua.ls Logo

YASKAWA GA800

YASKAWA GA800
644 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
2.3 b: Application
204 YASKAWA TOEPYAIGA8002B GA800 Drive Programming
1 : Analog Input
Use MFAI terminals A1, A2, and A3 to input an analog frequency reference with a voltage or current input signal.
Voltage Input
Refer to Table 2.20 to use a voltage signal input to one of the MFAI terminals.
Table 2.20 Frequency Reference Voltage Input
Terminal
Terminal Signal
Level
Parameter Settings
Note
Signal Level
Selection
Function Selection Gain Bias
A1 0 - 10 V H3-01 = 0 H3-02 = 0
[Frequency Reference]
H3-03 H3-04 Set DIP switch S1-1 to
V for voltage input.
-10 - +10 V H3-01 = 1
A2 0 - 10 V H3-09 = 0 H3-10 = 0
[Frequency Reference]
H3-11 H3-12 Set DIP switch S1-2 to
V for voltage input.
-10 - +10 V H3-09 = 1
A3 0 - 10 V H3-05 = 0 H3-06 = 0
[Frequency Reference]
H3-07 H3-08 Set DIP switch S1-3 to
V for voltage input.
Set DIP switch S4 to
AI for analog input.
-10 - +10 V H3-05 = 1
Figure 2.22 Example of Setting the Frequency Reference with a Voltage Signal to Terminal A1
Note:
You can also use this diagram to wire terminals A2 and A3.
Current Input
Refer to Table 2.21 to use a voltage signal input to one of the MFAI terminals.
Table 2.21 Frequency Reference Current Input
Terminal Signal Level
Parameter Settings
Note
Signal Level
Selection
Function Selection Gain Bias
A1 4 mA to 20 mA H3-01 = 2 H3-02 = 0
[Frequency Reference]
H3-03 H3-04 Set DIP switch S1-1 to
I for current input.
0 - 20 mA H3-01 = 3
A2 4 mA to 20 mA H3-09 = 2 H3-10 = 0
[Frequency Reference]
H3-11 H3-12 Set DIP switch S1-2 to
I for current input.
0 - 20 mA H3-09 = 3
A3 4 mA to 20 mA H3-05 = 2 H3-06 = 0
[Frequency Reference]
H3-07 H3-08 Set DIP switch S1-3 to
I for current input.
Set DIP switch S4 to
AI for analog input.
0 - 20 mA H3-05 = 3