Parameter Details
2
2.3 b: Application
YASKAWA TOEPYAIGA8002B GA800 Drive Programming 237
0 : Standard
1 : EZ Sleep/Wake-up
■ b5-90: EZ Sleep Unit
No.
(Hex.)
Name Description
Default
(Range)
b5-90
(0B90)
EZ Sleep Unit
Sets the measurement units for b5-91 [EZ Sleep Minimum Speed] and b5-92 [EZ Sleep Level].
0
(0, 1)
0 : 0.1Hz units
1 : rev/min
■ b5-91: EZ Sleep Minimum Speed
No.
(Hex.)
Name Description
Default
(Range)
b5-91
(0B91)
RUN
EZ Sleep Minimum Speed
Sets the minimum speed for the EZ Sleep/Wakeup function. This parameter uses the largest value
from b5-91, b5-34 [PID Output Lower Limit Level], and d2-02 [Frequency Reference Lower Limit].
0.0 Hz or 0 min
-1
(r/min)
(0.0 to 590.0 Hz or 0 to
35400 min
-1
(r/min))
Note:
The value of b5-90 [EZ Sleep Unit] sets the units. When b5-90 changes, this parameter does not automatically update. Set this parameter
again after you change b5-90 is changed.
■ b5-92: EZ Sleep Level
No.
(Hex.)
Name Description
Default
(Range)
b5-92
(0B92)
RUN
EZ Sleep Level
Sets the value that the output frequency or motor speed must be less than for longer than b5-93 [EZ
Sleep Time] to enter Sleep Mode.
0.0 Hz or 0 min
-1
(r/min)
(0.0 to 590.0 Hz or 0 to
35400 min
-1
(r/min))
Note:
When b5-90 [EZ Sleep Unit] changes, this parameter does not automatically update. Set this parameter again after you change b5-90.
■ b5-93: EZ Sleep Time
No.
(Hex.)
Name Description
Default
(Range)
b5-93
(0B93)
RUN
EZ Sleep Time
Sets the length of time that the output frequency or motor speed must be less than b5-92 [EZ Sleep
Level] to enter Sleep Mode.
5.0 s
(0.0 - 1000.0 s)
■ b5-94: EZ Sleep Wake-up Level
No.
(Hex.)
Name Description
Default
(Range)
b5-94
(0B94)
RUN
EZ Sleep Wake-up Level
Sets the level at which the drive resumes operation when exiting Sleep Mode.
0.00%
(0.00 - 600.00%)
Note:
The values of b5-20 [PID Unit Selection], b5-38 [PID User Unit Display Scaling], and b5-39 [PID User Unit Display Digits] set the units.
When b5-20, b5-38, and b5-39 change, this parameter does not automatically update. Set this parameter again after you change b5-20, b5-38,
and b5-39 are changed.
• When b5-95 = 0 [EZ Sleep Wake-up Mode = Absolute]:
When b5-09 = 0 [PID Output Level Selection = Normal Output (Direct Acting)], and the PID Feedback [H3-xx =
B] is less than the value of b5-94 for a time longer than the value of b5-96 [EZ Sleep Wake-up Time], the drive will
exit sleep and start operation again. When b5-09 = 1 [Reverse Output (Reverse Acting)], and the PID feedback is
more than setting value of b5-94 for a time longer than the setting value of b5-96, the drive will exit sleep and start
operation again.
• When b5-95 = 1 [Setpoint Delta]: