EasyManua.ls Logo

YASKAWA GA800

YASKAWA GA800
644 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Parameter Details
2
2.6 E: Motor Parameters
YASKAWA TOEPYAIGA8002B GA800 Drive Programming 311
E5-01: PM Motor Code Selection
No.
(Hex.)
Name Description
Default
(Range)
E5-01
(0329)
PM Motor Code Selection
Sets the motor code for Yaskawa PM motors. The drive uses the motor code to set some parameters
to their correct settings automatically.
FFFF
(0000 - FFFF)
Note:
If the drive hunts or shows an alarm after you use a motor code, use the keypad to enter the value shown on the nameplate to E5-xx.
When you use a PM motor other than a Yaskawa SMRA, SSR1, or SST4 series, set E5-01 = FFFF.
Figure 2.73 gives information about the motor code setting digits.
Figure 2.73 PM Motor Code
E5-02: PM Motor Rated Power
No.
(Hex.)
Name Description
Default
(Range)
E5-02
(032A)
PM Motor Rated Power
Sets the PM motor rated output in the units set in o1-58 [Motor Power Unit Selection].
Determined by o2-04, C6-01
(0.10 - 650.00 HP)
The drive will automatically set this parameter the next time you do Auto-Tuning.
PM Motor Parameter Settings
PM Stationary Auto-Tuning
PM Rotational Auto-Tuning
E5-03: PM Motor Rated Current (FLA)
No.
(Hex.)
Name Description
Default
(Range)
E5-03
(032B)
PM Motor Rated Current
(FLA)
Sets the PM motor rated current (FLA).
Determined by o2-04, C6-01
(10% to 200% of the drive
rated current)
Note:
When the drive model changes, the display units for this parameter also change.
0.01 A: models 2004 to 2042, 4002 to 4023
0.1 A: models 2056 to 2415, 4031 to 4720
After you do these types of Auto-Tuning, the drive automatically will set E5-03 to the value input for PM Motor
Rated Current:
PM Motor Parameter Settings
PM Stationary Auto-Tuning
PM StaTun for Stator Resistance
PM Rotational Auto-Tuning
E5-04: PM Motor Pole Count
No.
(Hex.)
Name Description
Default
(Range)
E5-04
(032C)
PM Motor Pole Count
Sets the number of PM motor poles.
4
(2 - 120)
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM OLV/PM
AOLV/PM
CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM OLV/PM
AOLV/PM
CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM OLV/PM
AOLV/PM
CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM OLV/PM
AOLV/PM
CLV/PM
EZOLV

Table of Contents

Other manuals for YASKAWA GA800

Related product manuals