Parameter Details
2
2.6 E: Motor Parameters
YASKAWA TOEPYAIGA8002B GA800 Drive Programming 311
■ E5-01: PM Motor Code Selection
No.
(Hex.)
Name Description
Default
(Range)
E5-01
(0329)
PM Motor Code Selection
Sets the motor code for Yaskawa PM motors. The drive uses the motor code to set some parameters
to their correct settings automatically.
FFFF
(0000 - FFFF)
Note:
• If the drive hunts or shows an alarm after you use a motor code, use the keypad to enter the value shown on the nameplate to E5-xx.
• When you use a PM motor other than a Yaskawa SMRA, SSR1, or SST4 series, set E5-01 = FFFF.
Figure 2.73 gives information about the motor code setting digits.
Figure 2.73 PM Motor Code
■ E5-02: PM Motor Rated Power
No.
(Hex.)
Name Description
Default
(Range)
E5-02
(032A)
PM Motor Rated Power
Sets the PM motor rated output in the units set in o1-58 [Motor Power Unit Selection].
Determined by o2-04, C6-01
(0.10 - 650.00 HP)
The drive will automatically set this parameter the next time you do Auto-Tuning.
• PM Motor Parameter Settings
• PM Stationary Auto-Tuning
• PM Rotational Auto-Tuning
■ E5-03: PM Motor Rated Current (FLA)
No.
(Hex.)
Name Description
Default
(Range)
E5-03
(032B)
PM Motor Rated Current
(FLA)
Sets the PM motor rated current (FLA).
Determined by o2-04, C6-01
(10% to 200% of the drive
rated current)
Note:
When the drive model changes, the display units for this parameter also change.
• 0.01 A: models 2004 to 2042, 4002 to 4023
• 0.1 A: models 2056 to 2415, 4031 to 4720
After you do these types of Auto-Tuning, the drive automatically will set E5-03 to the value input for “PM Motor
Rated Current”:
• PM Motor Parameter Settings
• PM Stationary Auto-Tuning
• PM StaTun for Stator Resistance
• PM Rotational Auto-Tuning
■ E5-04: PM Motor Pole Count
No.
(Hex.)
Name Description
Default
(Range)
E5-04
(032C)
PM Motor Pole Count
Sets the number of PM motor poles.
4
(2 - 120)