EasyManua.ls Logo

YASKAWA GA800 - Page 387

YASKAWA GA800
644 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Parameter Details
2
2.8 H: Terminal Functions
YASKAWA TOEPYAIGA8002B GA800 Drive Programming 387
H2-31: Comparator 2 Off-Delay Time
No.
(Hex.)
Name Description
Default
(Range)
H2-31
(154B)
Comparator 2 Off-Delay
Time
Sets the off-delay time for comparator 2.
0.0 s
(0.0 - 600.0 s)
Note:
For information on the comparator function, refer to 66: Comparator1 on page 404 and 67: Comparator2 on page 404.
H2-32: Comparator 1 Filter Time
No.
(Hex.)
Name Description
Default
(Range)
H2-32
(159A)
Comparator 1 Filter Time
Sets the time constant that is applied to the primary delay filter used for the analog output of the
monitor selected with H2-20 [Comparator 1 Monitor Selection].
0.0s
(0.0 - 10.0 s)
Note:
For information on the comparator function, refer to 66: Comparator1 on page 404 and 67: Comparator2 on page 404.
H2-33: Comparator1 Protection Selection
No.
(Hex.)
Name Description
Default
(Range)
H2-33
(159B)
Comparator1 Protection
Selection
Sets drive operation when it detects CP1 [Comparator1 Limit Fault].
4
(0 - 4)
0 : Ramp to Stop
The drive ramps the motor to stop in the deceleration time. Fault relay output terminal MA-MC turns ON, and MB-
MC turns OFF.
1 : Coast to Stop
The output turns off and the motor coasts to stop. Fault relay output terminal MA-MC turns ON, and MB-MC turns
OFF.
2 : Fast Stop (Use C1-09)
The drive stops the motor in the deceleration time set in C1-09 [Fast Stop Time]. Fault relay output terminal MA-MC
turns ON, and MB-MC turns OFF.
3 : Alarm Only
The keypad shows CP1 and the drive continues operation at the current frequency reference.
Note:
The output terminal set for Alarm [H2-01 to H2-03 = 10] activates.
4 : Digital Output Only
H2-34: Comparator 2 Filter Time
No.
(Hex.)
Name Description
Default
(Range)
H2-34
(159C)
Comparator 2 Filter Time
Sets the time constant that is applied to the primary delay filter used for the analog output of the
monitor selected with H2-26 [Comparator 2 Monitor Selection].
0.0s
(0.0 - 10.0 s)
H2-35: Comparator2 Protection Selection
No.
(Hex.)
Name Description
Default
(Range)
H2-35
(159D)
Comparator2 Protection
Selection
Sets drive operation when it detects CP2 [Comparator2 Limit Fault].
4
(0 - 4)
0 : Ramp to Stop
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM OLV/PM
AOLV/PM
CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM OLV/PM
AOLV/PM
CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM OLV/PM
AOLV/PM
CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM OLV/PM
AOLV/PM
CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM OLV/PM
AOLV/PM
CLV/PM
EZOLV

Table of Contents

Other manuals for YASKAWA GA800

Related product manuals