Parameter Details
2
2.8 H: Terminal Functions
YASKAWA TOEPYAIGA8002B GA800 Drive Programming 393
Note:
Figure 2.93 shows the result of the configuration when L4-07 = 1 [Speed Agree Detection Selection = Detection Always Enabled]. The
default setting of L4-07 is 0 [No detection during baseblock]. When the speed agreement detection selection is No Detection during
Baseblock, the terminal is deactivated when the drive output stops.
5: Frequency Detection 2
Setting Value Function Description
5 Frequency Detection 2
The terminal activates when the output frequency is higher than the value of L4-01 [Speed Agree Detection Level]. After the
terminal activates, the terminal stays activated until the output frequency = L4-01 - L4-02.
Note:
The detection function operates in the two motor rotation directions. The drive uses the L4-01 value as the forward/reverse detection level.
The drive outputs the motor speed status when A1-02 = 3, 7 [CLV, CLV/PM]. It also outputs the motor speed status when A1-02 = 4 and n4-
72 = 1.
ON : The output frequency is higher than the value of L4-01.
OFF : The output frequency < L4-01 - L4-02”, or L4-01.
Figure 2.94 Frequency Detection 2 Time Chart
6: Drive ready
Setting Value Function Description
6 Drive ready
The terminal activates when the drive is ready and running.
The terminal deactivates in these conditions:
When the power supply is OFF
During a fault
When there is problem with the control power supply
When there is a parameter configuration error and the drive cannot operate although there is a Run command
When you enter a Run command and it immediately triggers an overvoltage or undervoltage fault because the drive
has an overvoltage or undervoltage fault during stop
When the drive is in Programming Mode and will not accept a Run command
7: DC Bus Undervoltage
Setting Value Function Description
7 DC Bus Undervoltage
The terminal activates when the DC bus voltage or control circuit power supply is less than the voltage set with L2-05
[Undervoltage Detection Lvl (Uv1)]. The terminal also turns on when there is a fault with the DC bus voltage.
ON : The DC bus voltage is less than the setting value of L2-05.
OFF : The DC bus voltage is more than the setting value of L2-05.
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM OLV/PM
AOLV/PM
CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM OLV/PM
AOLV/PM
CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM OLV/PM
AOLV/PM
CLV/PM
EZOLV