2.8 H: Terminal Functions
394 YASKAWA TOEPYAIGA8002B GA800 Drive Programming
■ 8: During Baseblock (N.O.)
Setting Value Function Description
8 During Baseblock (N.O.)
The terminal turns on during baseblock. When the drive is in baseblock, the drive output transistor stops switching and does not
make DC bus voltage.
ON : During baseblock
OFF : The drive is not in baseblock.
■ 9: Frequency Reference from Keypad
Setting Value Function Description
9 Frequency Reference from
Keypad
Shows the selected frequency reference source.
ON : The keypad is the frequency reference source.
OFF : b1-01 or b1-15 [Frequency Reference Selection 1 or 2] is the frequency reference source.
■ A: Run Command from Keypad
Setting Value Function Description
A Run Command Source
Shows the selected Run command source.
ON : The keypad is the Run command source.
OFF : b1-02 or b1-16 [Run Command Selection 1 or 2] is the Run command source.
■ B: Torque Detection 1 (N.O.)
Setting Value Function Description
B Torque Detection 1 (N.O.)
The terminal activates when the drive detects overtorque or undertorque.
ON : The output current/torque is more than the torque value set with L6-02 [Torque Detection Level
1], or the level is less than the torque value set with L6-02 for longer than the time set with L6-03
[Torque Detection Time 1].
Note:
• When L6-01 ≥ 5, the drive will detect when the output current/torque is less than the detection level of L6-02 for longer than the time set in
L6-03.
• Refer to “L6: Torque Detection” for more information.
■ C: Frequency Reference Loss
Setting Value Function Description
C Frequency Reference Loss
The terminal activates when the drive detects a loss of frequency reference.
Note:
Refer to “L4-05: Fref Loss Detection Selection” for more information.
■ D: Braking Resistor Fault
Setting Value Function Description
D Braking Resistor Fault
The terminal activates when the mounting-type braking resistor is overheating or when there is a braking transistor fault.