2.8 H: Terminal Functions
396 YASKAWA TOEPYAIGA8002B GA800 Drive Programming
Figure 2.95 Speed Agree 2 Time Chart
■ 14: User-Set Speed Agree 2
Setting Value Function Description
14 User-Set Speed Agree 2
The terminal activates when the output frequency is in the range of L4-03 [Speed Agree Detection Level (+/-)] ± L4-04 [Speed
Agree Detection Width (+/-)] and in the range of the frequency reference ± L4-04.
Note:
• The detection level set in L4-03 is a signed value. The drive will only detect in one direction.
• The drive outputs the motor speed status when A1-02 = 3, 7 [Control Method Selection = CLV, CLV/PM].
ON : The output frequency is in the range of “L4-03 ± L4-04” and the range of frequency reference ±
L4-04.
OFF : The output frequency is not in the range of “L4-03 ± L4-04” or the range of frequency
reference ± L4-04.
Figure 2.96 Example of User-set Speed Agree 2 (L4-03 Is Positive)
■ 15: Frequency Detection 3
Setting Value Function Description
15 Frequency Detection 3
The terminal deactivates when the output frequency is higher than the value of “L4-03 [Speed Agree Detection Level (+/-)] + L4-04
[Speed Agree Detection Width (+/-)]”. After the terminal deactivates, the terminal stays off until the output frequency is at the value
of L4-03.
Note:
• The detection level set in L4-03 is a signed value. The drive will only detect in one direction.
• The drive outputs the motor speed status when A1-02 = 3, 7 [Control Method Selection = CLV, CLV/PM].
ON : The output frequency is less than the value of L4-03 or is not higher than the value of L4-03 +
L4-04.