Configuring LD 800DN Linking Device Unit Section 4 Configuration
112 9ARD000014-600 A
Tabl e 17. Settings for LD 800DN Linking Device Unit
Parameter Data Type Unit Min Max
Editable
/Read
Only
Description
Vendor ID INT - - - Read
Only
ABB vendor Identification number.
Product
Ty p e
INT - - - Read
Only
Device Type to identify the device
profile of LD 800DN as
Communication adapter
device(0x0C).
Product
Code
INT - - - Read
Only
Identification number for the linking
device within the communication
adapter profile of adapter.
Major
Revision
INT - - - Read
Only
Major revision of the linking device.
Minor
Revision
INT - - - Read
Only
Minor revision of the linking device.
Electronic
Key
VendorID
0 1 Editable Criteria that can be specified by user
for LD 800DN to accept connection
from CI873 only when Vendor ID of
LD 800DN configured in Control
Builder matches with the Vendor ID of
LD 800DN device in the network.
Values are:
Enable Keying, Disable Keying
Upon modification, connection
between LD 800DN and CI873 gets
disconnected and connected again.
Hence communication with
DeviceNet slaves stop momentarily.