Table 21. Strobe Connection Parameters
Parameter Default Value
Data
Ty
pe
Read Only /
Editable
Description
Strobe
Co
nnection
Enabled
Depends on
the device
support as
stated in its
EDS file.
Enum Editable Enable or disable the connection. If
ena
bled, linking device communicates
with the device over the Strobe
connection
Values are: Enabled and Disabled.
Conn Strobe
In
putSize
Depends on
the device
support as
stated in its
EDS file.
Int Read Only Number of bytes of data that gets
t
ransferred from the device to the linking
device, over the Strobe connection.
Conn Strobe
Out
putSize
Depends on
the device
support as
stated in its
EDS file.
Int Read Only Number of bytes of data that gets
tr
ansferred from linking device to the
device, over the Strobe connection.
Section 4 Configuration Communication Related Parameters
9ARD000014-600 A 129
Cyclic Connection
The Cyclic Connection parameters in the hardware editor are described in Table 22.
Upon modification of editable parameters, the connection between LD 800DN and
all DeviceNet slaves configured under it, stops momentarily.