Section 4 Configuration Configuring EtherNet/IP Device
9ARD000014-600 A 139
Electronic
Key Major
Revision
Enum 0 2 Editable Criteria that can be specified by user
for EtherNet/IP to accept connection
from CI873 only when major revision
of EtherNet/IP configured in Control
Builder matches or is greater than the
major revision of EtherNet/IP device
in the network.
Values are:
Disable Keying, Exact Match, Current
and Higher
Upon modification, connection
between EtherNet/IP and CI873 gets
disconnected and connected again.
IP
Address
(1)
String - - - Editable The IP address of the EtherNet/IP
device on the network. It must be an
IP address on the same subnet as
where the CI873 is placed.
If the IP address is blank, then first
three fields are taken from its parent
CI873 IP address and the fourth is
taken from its hardware tree position.
Upon modification, connection of
CI873 with the EtherNet/IP Device is
re-established.
Class
1ExclusiveO
wner
O2TRPI
Dint ms 10 500 Editable Requested Packet Interval in
milliseconds for O->T packets.
Upon modification, connection with
the Ethernet/IP device is re-
established.
Table 23. Settings for EtherNet/IP Device Unit (Continued)
Parameter Data Type Unit Min Max
Editable
/Read
Only
Description