146 Parameters
In1P Start; In2 Stop;
In3 Dir
The sources of the start and stop commands are selected
by parameters 20.08 Ext2 in1 source and 20.09 Ext1 in2
source. The source selected by 20.10 Ext2 in3 source
determines the direction. The state transitions of the
source bits are interpreted as follows:
Notes:
Parameter 20.07 Ext2 start trigger type has no effect
with this setting.
When source 2 is 0, the Start and Stop keys on the
control panel are disabled.
5
In1P Start fwd; In2P
Start rev; In3 Stop
The sources of the start and stop commands are selected
by parameters 20.08 Ext2 in1 source, 20.09 Ext1 in2
source and 20.10 Ext2 in3 source. The source selected by
20.10 Ext2 in3 source determines the direction. The state
transitions of the source bits are interpreted as follows:
Note: Parameter 20.07 Ext2 start trigger type has no
effect with this setting.
6
Control panel Start; stop and direction commands through control panel;
when EXT1 is active. Applies also for PC-Tool when it is
connected via panel port.
11
Embedded fieldbus Start; stop and direction commands through embedded
fieldbus protocol when EXT1 is active.
Note: The start signal is always level-triggered with this
setting regardless of parameter 20.02 Ext1 start trigger
type.
14
Integrated Panel Start; stop and direction commands from Integrated Panel 23
20.07 Ext2 start trigger type Defines whether the start signal for external control
location EXT2 is edge-triggered or level-triggered.
Note: This parameter is not effective if a pulse-type start
signal is selected. See the descriptions of the selections of
parameter 20.06 Ext2 commands.
Level
Edge The start signal is edge-triggered. 0
Level The start signal is level-triggered. 1
20.08 Ext2 in1 source Selects source 1 for parameter 20.06 Ext2 commands.
For the available selections, see parameter 20.03 Ext1 in1
source.
Always off
No. Name/Value Description Default
FbEq 16
State of
source 1
(20.08)
State of
source 2
(20.09)
State of
source 3
(20.10)
Command
0
-
> 1 1 0 Start forward
0
-
> 1 1 1 Start reverse
Any 0 Any Stop
State of
source 1
(20.08)
State of
source 2
(20.09)
State of
source 3
(20.10)
Command
0
-
> 1 Any 1 Start forward
Any 0
-
> 1 1 Start reverse
Any Any 0 Stop