Parameters 199
30.11 Minimum speed Defines together with 30.12 Maximum speed allowed
speed range. See the figure below.
A positive (or zero) minimum speed value defines two
ranges, one positive and one negative.
A negative minimum speed value defines one range.
WARNING! The absolute value of 30.11 Minimum
speed must not be higher than the 30.12 Maximum
speed.
WARNING! In speed control mode only. In
frequency control mode, use frequency limits
(30.13 and 30.14).
-1500.00
rpm
-30000.00…30000.00
rpm
Minimum allowed speed. See par.
46.01
30.12 Maximum speed Defines together with 30.11 Minimum speed allowed
speed range. See parameter 30.11 Minimum speed.
Note: This parameter does not affect the speed
acceleration and deceleration ramp times. See parameter
46.01 Speed scaling.
WARNING! The absolute value of 30.12 Maximum
speed must not be lower than 30.11 Minimum
speed.
WARNING! In speed control mode only. In
frequency control mode, use frequency limits
(30.13 and 30.14).
1500.00 rpm
-30000.00… 30000.00
rpm
Maximum speed. See par.
46.01
No. Name/Value Description Default
FbEq 16
Speed
Speed range allowed
Speed range allowed
Speed range allowed
Time
Speed
Time
0
0
30.11 value is < 0
30.12
30.11
30.11 value is >
0
30.12
30.11
-30.11
-30.12
ACS180 FW.book Page 199 Tuesday, March 9, 2021 2:25 PM