172 Actual signals and parameters
0161 PULSE INPUT
FREQ
Value of frequency input in Hz 1 = 1 Hz
0162 RO STATUS Status of relay output 1. 1 = RO is energized, 0 = RO is de-
energized.
1 = 1
0163 TO STATUS Status of transistor output, when transistor output is used as
a digital output.
1 = 1
0164 TO
FREQUENCY
Transistor output frequency, when transistor output is used
as a frequency output.
1 = 1 Hz
0173 RO 2-4
STATUS
Status of the relays in the MREL relay output extension
module. See MREL-01 relay output extension module
user's manual (3AUA0000035974 [English]).
Example: 100 = RO 2 is on, RO 3 and RO 4 are off.
0174 SAVED KWH Energy saved in kWh compared to the energy used when
the pump is connected directly to the supply. See the note
on page 256.
The counter value is accumulated till it reaches 999.9, after
which the counter rolls over and starts again from 0.0, and
the counter value of signal 0175 is incremented by one. Can
be reset with parameter 4509 ENERGY RESET (resets all
energy calculators at the same time). See group 45
ENERGY SAVING.
1 =
0.1 kWh
0175 SAVED MWH Energy saved in MWh compared to the energy used when
the pump is connected directly to the supply. See the note
on page 256.
The counter value is accumulated till it reaches 65535, after
which the counter rolls over and starts again from 0. Can be
reset with parameter 4509 ENERGY RESET (resets all
energy calculators at the same time). See group 45
ENERGY SAVING.
1 =
1MWh
0176 SAVED
AMOUNT 1
Energy saved in local currency (remainder when the total
saved energy is divided by 1000). See the note on page
256.
To find out the total saved energy in currency units, add the
value of signal 0177 multiplied by 1000 to the value of signal
0176.
Example:
0176 SAVED AMOUNT 1 = 123.4
0177 SAVED AMOUNT 2 = 5
Total saved energy = 5 · 1000 + 123.4 = 5123.4 currency
units.
The counter value is accumulated till it reaches 999.9, after
which the counter rolls over and starts again from 0.0, and
the counter value of signal 0177 is incremented by one. Can
be reset with parameter 4509 ENERGY RESET (resets all
energy calculators at the same time). Local energy price is
set with parameter 4502 ENERGY PRICE. See group 45
ENERGY SAVING.
1 = 0.1
(Currency)
0177 SAVED
AMOUNT 2
Energy saved in local currency in thousand currency units.
Eg v
alue 5 means 5000 currency units. See the note on
page 256.
The counter value is accumulated till it reaches 65535 (the
counter does not roll over). See signal 0176 SAVED
AMOUNT 1.
1 = 1000
(Currency)