242 Actual signals and parameters
DI3 See selection DI1.3
DI4 See selection DI1.4
DI5 See selection DI1.5
INTERNAL Activated and deactivated automatically as defined by
parameters 4023 PID SLEEP LEVEL and 4025 WAKE-UP
DEV.
7
SUPRV1
OVER
The function is activated when parameter 3201 SUPERV 1
PARAM stays over the high limit defined by parameter 3203
SUPERV 1 LIM HI.
The internal sleep criteria set by parameters 4023 PID
SLEEP LEVEL and 4025 WAKE-UP DEV are not effective.
The sleep start and stop delay parameters 4024 PID SLEEP
DELAY and 4026 WAKE-UP DELAY are effective.
9
SUPRV2
OVER
See selection SUPRV1 OVER. 10
SUPRV3
OVER
See selection SUPRV1 OVER.11
DI1(INV) The function is activated/deactivated through inverted digital
input DI1. 1 = deactivation, 0 = activation.
The internal sleep criteria set by parameters 4023 PID
SLEEP LEVEL and 4025 WAKE-UP DEV are not effective.
The sleep start and stop delay parameters 4024 PID SLEEP
DELAY and 4026 WAKE-UP DELAY are effective.
-1
DI2(INV) See selection DI1(INV).-2
DI3(INV) See selection DI1(INV).-3
DI4(INV) See selection DI1(INV).-4
DI5(INV) See selection DI1(INV).-5
SUPRV1
UN
DER
The function is activated when parameter 3201 SUPERV 1
PARAM stays below the low limit defined by parameter 3202
SUPERV 1 LIM LO.
The internal sleep criteria set by parameters 4023 PID
SLEEP LEVEL and 4025 WAKE-UP DEV are not effective.
The sleep start and stop delay parameters 4024 PID SLEEP
DELAY and 4026 WAKE-UP DELAY are effective.
-9
SUPRV2
UNDER
See selection SUPRV1 UNDER. -10
SUPRV3
UNDER
See selection SUPRV1 UNDER.-11
All parameters
No. Name/Value Description Def/FbEq