268 Actual signals and parameters
8113 LOW FREQ 2 Sets the frequency limit used to stop the second auxiliary
motor. See 8112 LOW FREQ 1 for a complete description of
the operation.
The second auxiliary motor stops if:
• two auxiliary motors are running
• drive output frequency drops below limit 8113 - 1 Hz
• output frequency stays below the relaxed limit (8113 +
1 Hz) for at least time 8116 AUX MOT STOP D.
E: 25.0 Hz
U: 30.0 Hz
0.0…500.0 Hz Frequency 1 = 0.1 Hz
8114 LOW FREQ 3 Sets the frequency limit used to stop the third auxiliary
motor. See 8112 LOW FREQ 1 for a complete description of
the operation.
The third auxiliary motor stops if:
• three auxiliary motors are running
• drive output frequency drops below limit 8114 - 1 Hz
• output frequency stays below the relaxed limit (8114 +
1 Hz) for at least time 8116 AUX MOT STOP D.
E: 25.0 Hz
U: 30.0 Hz
0.0…500.0 Hz Frequency 1 = 0.1 Hz
8115 AUX MOT
START D
Sets the start delay for the auxiliary motors.
The output frequency must remain above the start
frequency limit (parameter 8109, 8110 or 8111) for this time
period before the auxiliary motor starts.
See 8109 START FREQ 1 for a complete description of the
operation.
5.0 s
0.0…3600.0 s Delay time 1 = 0.1 s
8116 AUX MOT
STOP D
Sets the stop delay for the auxiliary motors.
The output frequency must remain below the low frequency
limit (parameter 8112, 8113 or 8114) for this time period
before the auxiliary motor stops.
See 8112 LOW FREQ 1 for a complete description of the
operation.
3.0 s
0.0…3600.0 s Delay time 1 = 0.1 s