Fieldbus control with the embedded fieldbus 305
10 ABOVE_LIMIT 1 Supervised parameter value exceeds the supervision high
limit. Bit value is 1 until the supervised parameter value falls
below the supervision low limit. See parameter group 32
SUPERVISION.
0 Supervised parameter value falls below the supervision low
limit. Bit value is 0 until the supervised parameter value
exceeds the supervision high limit. See parameter group 32
SUPERVISION.
11 EXT CTRL LOC 1 External control location EXT2 selected
0 External control location EXT1 selected
12 EXT RUN
ENABLE
1 External Run enable signal received
0 No external Run enable received
13 MOTOR_HEAT 1 Motor heating is On
0 Motor heating is Off
14…
15
Reserved
ABB drives profile (EFB) Status word, parameter 5320 EFB PAR 20
Bit Name Value STATE/Description
(Correspond to states/boxes in the state diagram)