114 Parameters
06.18 Start inhibit status
word
Start inhibit status word. This word specifies the source of
the inhibiting signal that is preventing the drive from
starting.
The conditions marked with an asterisk (*) only require
that the start command is cycled. In all other instances,
the inhibiting condition must be removed first.
See also parameter 06.16 Drive status word 1, bit 1.
This parameter is read-only.
-
0000h…FFFFh Start inhibit status word. 1 = 1
No. Name/Value Description Default
FbEq 16
Bit Name Description
0 Not ready run 1 = DC voltage is missing or drive has not been parametrized
correctly. Check the parameters in groups 95 and 99.
1 Ctrl location changed * 1 = Control location has changed
2 SSW inhibit 1 = Control program is keeping itself in inhibited state
3 Fault reset * 1 = A fault has been reset
4 Lost start enable 1 = Start enable signal missing
5 Lost run enable 1 = Run enable signal missing
6 Reserved
7 STO 1 = Safe torque off function active
8 Current calibration
ended
* 1 = Current calibration routine has finished
9 ID run ended * 1 = Motor identification run has finished
10 Reserved -
11 Em Off1 1 = Emergency stop signal (mode off1)
12 Em Off2 1 = Emergency stop signal (mode off2)
13 Em Off3 1 = Emergency stop signal (mode off3)
14 Auto reset inhibit 1 = The autoreset function is inhibiting operation
15 Jogging active 1 = The jogging enable signal is inhibiting operation