148 Parameters
Supervision 2 Bit 1 of 32.01 Supervision status.25
Supervision 3 Bit 2 of 32.01 Supervision status.26
Supervision 4 Bit 3 of 32.01 Supervision status.27
Supervision 5 Bit 4 of 32.01 Supervision status.28
Supervision 6 Bit 5 of 32.01 Supervision status.29
FBA A MCW bit 3 Control word bit 3 received through fieldbus interface A. 30
EFB MCW bit 3 Control word bit 3 received through the embedded
fieldbus interface.
32
Other [bit] Source selection (see Terms and abbreviations). -
20.13 Run enable 2 Selects the source of the auxiliary external run enable
signal. If the run enable signal is switched off, the drive will
not start, or coasts to stop if running. 1 = Run enable.
Note: If Run enable signal is lost while running, drive stops
according to active stop mode (see parameter stop
mode).
Note: This parameter cannot be changed while the drive is
running.
See parameter 20.12 for the available selections.
Selected
20.14 Run enable 3 Selects the source of the 2 auxiliary external run enable
signal. If the run enable signal is switched off, the drive will
not start, or coasts to stop if running. 1 = Run enable.
Note: If Run enable signal is lost while running, drive stops
according to active stop mode (see parameter stop
mode).
Note: This parameter cannot be changed while the drive is
running.
See parameter 20.12 for the available selections.
Selected
20.15 Run enable 4 Selects the source of the 3 auxiliary external run enable
signal. If the run enable signal is switched off, the drive will
not start, or coasts to stop if running. 1 = Run enable.
Note: If Run enable signal is lost while running, drive stops
according to active stop mode (see parameter stop
mode).
Note: This parameter cannot be changed while the drive is
running.
See parameter 20.12 for the available selections.
Selected
20.19 Enable start signal Selects the source for the start enable signal.
1 = Start enable.
With the signal switched off, any drive start command is
inhibited. (Switching the signal off while the drive is
running will not stop the drive.)
See also parameter 20.12 Run enable 1.
Selected
Not selected 0. 0
Selected 1. 1
DI1 Digital input DI1 (10.02 DI delayed status, bit 0). 2
DI2 Digital input DI2 (10.02 DI delayed status, bit 1). 3
DI3 Digital input DI3 (10.02 DI delayed status, bit 2). 4
DI4 Digital input DI4 (10.02 DI delayed status, bit 3). 5
No. Name/Value Description Default
FbEq 16