EasyManua.ls Logo

ABB ACS380 Series - Page 191

ABB ACS380 Series
462 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Parameters 191
28.51 Critical frequency
function
Enables/disables the critical frequencies function. Also
determines whether the specified ranges are effective in
both rotating directions or not.
See also section Critical speeds/frequencies on page 63.
00b
00b…11b Critical frequencies configuration word. 1 = 1
28.52 Critical frequency 1
low
Defines the low limit for critical frequency 1.
Note: This value must be less than or equal to the value
of 28.53 Critical frequency 1 high.
0.00 Hz
-500.00…500.00 Hz Low limit for critical frequency 1. See par.
46.02
28.53 Critical frequency 1
high
Defines the high limit for critical frequency 1.
Note: This value must be greater than or equal to the
value of 28.52 Critical frequency 1 low.
0.00 Hz
-500.00…500.00 Hz High limit for critical frequency 1. See par.
46.02
28.54 Critical frequency 2
low
Defines the low limit for critical frequency 2.
Note: This value must be less than or equal to the value
of 28.55 Critical frequency 2 high.
0.00 Hz
-500.00…500.00 Hz Low limit for critical frequency 2. See par.
46.02
28.55 Critical frequency 2
high
Defines the high limit for critical frequency 2.
Note: This value must be greater than or equal to the
value of 28.54 Critical frequency 2 low.
0.00 Hz
-500.00…500.00 Hz High limit for critical frequency 2. See par.
46.02
28.56 Critical frequency 3
low
Defines the low limit for critical frequency 3.
Note: This value must be less than or equal to the value
of 28.57 Critical frequency 3 high.
0.00 Hz
-500.00…500.00 Hz Low limit for critical frequency 3. See par.
46.02
28.57 Critical frequency 3
high
Defines the high limit for critical frequency 3.
Note: This value must be greater than or equal to the
value of 28.56 Critical frequency 3 low.
0.00 Hz
-500.00…500.00 Hz High limit for critical frequency 3. See par.
46.02
No. Name/Value Description Default
FbEq 16
Bit Name Information
0 Crit freq 1 = Enable: Critical frequencies enabled.
0 = Disable: Critical frequencies disabled.
1 Sign mode 1 = According to par: The signs of parameters 28.5228.57 are taken
into account.
0 = Absolute: Parameters 28.5228.57 are handled as absolute values.
Each range is effective in both directions of rotation.

Table of Contents