28.23 Constant frequency
sel2
When bit 0 of parameter 28.21 Constant frequency
function is 0 (Separate), selects a source that activates
constant frequency 2.
When bit 0 of parameter 28.21 Constant frequency
function is 1 (Packed), this parameter and parameters
28.22 Constant frequency sel1 and 28.24 Constant
frequency sel3 select three sources that are used to
activate constant frequencies. See table at parameter
28.22 Constant frequency sel1.
For the selections, see parameter 28.22 Constant
frequency sel1.
Not selected
28.24 Constant frequency
sel3
When bit 0 of parameter 28.21 Constant frequency
function is 0 (Separate), selects a source that activates
constant frequency 3.
When bit 0 of parameter 28.21 Constant frequency
function is 1 (Packed), this parameter and parameters
28.22 Constant frequency sel1 and 28.23 Constant
frequency sel2 select three sources that are used to
activate constant frequencies. See table at parameter
28.22 Constant frequency sel1.
For the selections, see parameter 28.22 Constant
frequency sel1.
Not selected
28.26 Constant frequency 1 Defines constant frequency 1 (the frequency the motor will
turn when constant frequency 1 is selected).
5.00 Hz
-500.00…500.00 Hz Constant frequency 1. See par.
46.02
28.27 Constant frequency 2 Defines constant frequency 2. 10.00 Hz
-500.00…500.00 Hz Constant frequency 2. See par.
46.02
28.28 Constant frequency 3 Defines constant frequency 3. 15.00 Hz
-500.00…500.00 Hz Constant frequency 3. See par.
46.02
28.29 Constant frequency 4 Defines constant frequency 4. 20.00 Hz
-500.00…500.00 Hz Constant frequency 4. See par.
46.02
28.30 Constant frequency 5 Defines constant frequency 5. 25.00 Hz
-500.00…500.00 Hz Constant frequency 5. See par.
46.02
28.31 Constant frequency 6 Defines constant frequency 6. 40.00 Hz
-500.00…500.00 Hz Constant frequency 6. See par.
46.02
28.32 Constant frequency 7 Defines constant frequency 7. 50.00 Hz
-500.00…500.00 Hz Constant frequency 7. See par.
46.02
28.41 Frequency ref safe Defines a safe frequency reference value that is used with
supervision functions such as
• 12.03 AI supervision function
• 49.05 Communication loss action
• 50.02 FBA A comm loss func.
0.00 Hz
-500.00…500.00 Hz Safe frequency reference. See par.
46.02
No. Name/Value Description Default