6. Slide the cable through the hole of the bottom plate and attach the grommet to the
hole.
7. Connect the motor cable:
• Ground the shield 360 degrees by tightening the clamp of the power cable
grounding shelf onto the stripped part of the cable (7a).
• Connect the twisted shield of the cable to the grounding terminal (7b).
• Connect the phase conductors of the cable to the T1/U, T2/V and T3/W
terminals (7c). Tighten the screws to the torque given in the figure.
6
7b
7
7a
7c
Frame size T1/U, T2/V, T3/W PE,
N·m lbf·ft M N·m lbf·ft N·m lbf·ft
R5 5.6 4.1 M5 2.2 1.6 1.2 0.9