Electrical installation 113
Input power cable
10. Connect the input power cable as in step 9. Use terminals L1, L2 and L3.
Terminals T1/U, T2/V and T3/W
Remove the nut that attaches the connector to its busbar.
Put the conductor under the connector pressure plate and pre-tighten the
conductor.
Put the connector back to its busbar. Start the nut, and turn it at least two
rotations by hand.
WARNING! Before using tools, make sure that the nut/screw is not cross-
threading. Cross-threading will damage the drive and cause danger.
Tighten the nut to a torque of 30 N·m (22 lbf·ft).
Tighten the conductor(s) to 40 N·m (30 lbf·ft) for frame R8 or to 70 N·m
(52 lbf·ft) for frame R9.
8
M5×25/35
Frame size L1, L2, L3, T1/U, T2/V, T3/W PE,
N·m lbf·ft N·m m N·m lbf·ft
R6 30 22.1 9.8 7.2 1.2 0.9
R7 40 29.5 9.8 7.2 1.2 0.9
R8 40 29.5 9.8 7.2 1.2 0.9
R9 70 51.6 9.8 7.2 1.2 0.9