Parameters 141
13.29 AI6 max scale Defines the real value that corresponds to the maximum
analogue input AI6 value defined by parameter 13.27 AI6
max.
-32768.000 …
32768.000
Real value corresponding to maximum AI6 value. 1000 = 1
13.30 AI6 min scale Defines the real value that corresponds to the minimum
analogue input AI6 value defined by parameter 13.28 AI6
min. See the drawing at parameter 13.29 AI6 max scale.
-32768.000 …
32768.000
Real value corresponding to minimum AI6 value. 1000 = 1
13.31 AI tune Triggers the AI tuning function.
Connect the signal to the input and select the appropriate
tuning function.
No action AI tune is not activated. 0
AI1 min tune Current analogue input AI1 signal value is set as minimum
value of AI1 into parameter 13.03 AI1 min. The value reverts
back to No action automatically.
1
AI1 max tune Current analogue input AI1 signal value is set as maximum
value of AI1 into parameter 13.02 AI1 max. The value reverts
back to No action automatically.
2
AI2 min tune Current analogue input AI2 signal value is set as minimum
value of AI2 into parameter 13.08 AI2 min. The value reverts
back to No action automatically.
3
AI2 max tune Current analogue input AI2 signal value is set as maximum
value of AI2 into parameter 13.07 AI2 max. The value reverts
back to No action automatically.
4
13.32 AI superv func Selects how the drive reacts when analogue input signal limit
is reached. The limit is selected by parameter 13.33 AI superv
cw.
No No action taken. 0
Fault The drive trips on an AI SUPERVISION fault. 1