EasyManua.ls Logo

ABB OmniCore C90XT - Page 212

ABB OmniCore C90XT
450 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Note/IllustrationAction
Connect the adapter cable to the digital
base.
K5.1.X5 - A2.X4/K4.X7
Note
If the Ethernet extension switch is
installed, connect and disconnect
the connector K5.1.X5 to/from
K4.X7.
If the Ethernet extension switch is
not installed, connect and discon-
nect the connector K5.1.X5 to/from
A2.X4.
K5.1.X4 - K2.X3
The harness connected to I/O unit
by customer
4
Concluding procedure
Note/IllustrationAction
Closing the door on page 174.Close the door.1
Perform the function tests to verify that
the safety features work properly, see
Function tests on page 165.
2
212 Product manual - OmniCore C90XT
3HAC073706-001 Revision: D
© Copyright 2020-2021 ABB. All rights reserved.
5 Repair
5.2.7 Replacing the scalable I/O unit
Continued

Table of Contents

Related product manuals