Troubleshooting procedure
NoteAction
See LEDs on page 398.If the LEDs do not turn steady after
approximately 5 minutes then re-
start the controller and check the
LEDs again.
1
Force start the RobotWare Installa-
tion Utilities mode, see Controller
fails to start on page 374.
2
Re-install RobotWare, if possible.3
See Replacing the main computer on page 213.The main computer may be faulty,
replace it and verify that the fault
has been fixed.
4
400 Product manual - OmniCore C90XT
3HAC073706-001 Revision: D
© Copyright 2020-2021 ABB. All rights reserved.
7 Troubleshooting
7.3.9 Troubleshooting the main computer
Continued