19
149
19 - Troubleshooting
19�5�2 Controller self-oscillating
P-area too small or amplication too great. Increase the P-area or reduce the amplication until the
self-oscillation stops.
19�5�3 The controller error on the controller settings page is less than the dierence between
the actual value and the set value
This is not actually an error. The controller error on the settings page should never be more than half
the dened P-area. If this happens regularly, the P-area may be too small, causing the controller to
self-oscillate. Increase the P-area.