© Agilent Technologies 1989–2002 Agilent 3070 / 79000 Site Preparation 10-127
Chapter 10: Site Preparation – Power Requirements for Older Systems: Tester Power Requirements (Series I/II)
Table 10-30 307X Series II, E1131A power requirements for all power options
317X 327X 307X POTS Bay
Uses E1135 Testhead (PDU #1) Support Bay (PDU #2)
Full Load Amps (FLA)
36 NA 31 16 16
Breaker Size in Amps
40 NA 40 20 20
SO Cord Wire Size mm2 (American Wire Gauge - AWG)
6 (10) NA 10 (8) 4 (12) 4 (12)