P1 – Floor Level Network (FLN) G-7
Configurable points are inputs and outputs that let you read and write
parameter values. These objects handle only 15-bit parameter values
(0 – 32767).
Important: If a parameter has a decimal point, the value must be
properly scaled by the user. For example, Accel Time has
two decimal places. To use the value 60.00, the scaled
value 6000 must be communicated to the drive. The scaled
value 6000 will be returned.
Reading Parameter Values
The configurable points may show any parameter in the drive by
configuring the Param# in the Read Param point. The drive reads the
value of the parameter configured in the Param# for the Read Param
point and shows the result in the Read Value point. The Param# for the
Read Param point default to commonly accessed parameters and can be
changed if desired. A “0” disables the fetching of data and a “0” is
returned in the Read Value point. See Figure G.1
and Table G.4.
Figure G.1 Configurable Input Point Operation
Using P1 Configurable Points to Access Parameters
Table G.4 Configurable Points: Inputs
Point Name Description Default
36 Read Param Param# to read value 0
37 Read Value Value of parameter specified by Point 36 0
Controller
Drive
Set Point 36 with
Param# to Read
Data From.
Set Point 37 to get
Data of Param# in
Point 36.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Allen-Bradley PowerFlex400 and is the answer not in the manual?

Allen-Bradley PowerFlex400 Specifications

General IconGeneral
BrandAllen-Bradley
ModelPowerFlex400
CategoryController
LanguageEnglish

Related product manuals