Programming and Parameters 3-17
Terminal Block Group (continued)
T061 [Relay Out2 Level] Related Parameter(s): T060, T063, T064, d318
32 bit parameter.
Sets the trip point for the digital output relay if the value of T060
[Relay Out2 Sel] is 6, 7, 8, 9, 10 or 12.
Values Default: 0.0
Min/Max: 0.0/9999
Display: 0.1
32
T060 Setting T061 Min/Max
6
7
8
9
10
12
0/320 Hz
0/180%
0/815 Volts
0/100%
1/180 degs
0/1
T063 [Relay 2 On Time] Related Parameter(s): T060, T061, T064
Sets delay time before Relay energizes after required condition testing.
Values Default: 0.0 Secs
Min/Max: 0.0/600.0 Secs
Display: 0.1 Secs
T064 [Relay 2 Off Time] Related Parameter(s): T060, T061, T063
Sets delay time before Relay de-energizes after required condition testing ceases.
Important: Do not use this parameter with Auxiliary Motor Control mode AutoSwap enabled.
Values Default: 0.0 Secs
Min/Max: 0.0/600.0 Secs
Display: 0.1 Secs