3-6 Programming and Parameters
Basic Display Group (continued)
b011 [Elapsed MWh] Related Parameter(s): b015, A195
Accumulated output energy of the drive.
Values Default: Read Only
Min/Max: 0/3276.7
Display: 0.1 MWh
b012 [Elapsed Run Time] Related Parameter(s): A195
Displays the accumulated time that the drive has output power since the last A195 [Reset Meter].
Time is displayed in 10 hour increments.
Values Default: Read Only
Min/Max: 0/9999 Hrs
Display: 1 = 10 Hrs
b013 [Torque Current]
Displays the torque portion of the output current.
Values Default: Read Only
Min/Max: 0.0/(Drive Rated Amps × 2)
Display: 0.1 Amps
b014 [Drive Temp]
Present operating temperature of the drive power section.
Values Default: Read Only
Min/Max: 0/120 degC
Display: 1 degC
b015 [Elapsed kWh] Related Parameter(s): b011, A195
Accumulated output energy of the drive. This parameter works in conjunction with [Elapsed MWh].
When the maximum value of this parameter is reached, this parameter resets to zero and [Elapsed
MWh] is incremented.
Values Default: Read Only
Min/Max: 0.0/100.0 kWh
Display: 0.1 kWh