Programming and Parameters 3-5
Basic Display Group (continued)
b006 [Drive Status] Related Parameter(s): A166
Present operating condition of the drive.
Values Default: Read Only
Min/Max: 0/1
Display: 1
1 = Condition True, 0 = Condition False
Running Bit 1
Forward Bit 2
Accelerating Bit 3
Decelerating Bit 4
b007 [Fault 1 Code] Related Parameter(s): A186, A197, d307-d315
A code that represents a drive fault. [Fault 1 Code] is the most recent fault. Repetitive faults will only
be recorded once.
Refer to Chapter
4 for fault code descriptions.
Values Default: Read Only
Min/Max: 0/122
Display: 1
b008 [Process Display] Related Parameter(s): b001, A160
32 bit parameter.
The output frequency scaled by A160
[Process Factor].
Values Default: Read Only
Min/Max: 0.00/9999.99
Display: 0.01 – 1
32
Output
Freq
Process
Factor
Process
Display
=
x
b010 [Output Power]
Output power present at T1, T2 & T3 (U, V & W).
Values Default: Read Only
Min/Max: 0.0/999.9
Display: 0.1 kW