3-42 Programming and Parameters
Advance Program Group (continued)
A182 [Drive OL Mode] Related Parameter(s): P032, P033
Determines how the drive handles overload conditions that would otherwise cause the drive to fault.
Options 0 “DIsabled”
1 “Reduce CLim”
2 “Reduce PWM”
3 “Both-PWM 1st” (Default)
A183 [SW Current Trip] Related Parameter(s): P033
Enables/disables a software instantaneous (within 100 ms) current trip.
Values Default: 0.0 (Disabled)
Min/Max: 0.0/(Drive Rated Amps × 1.8)
Display: 0.1 Amps
A184 [Load Loss Level] Related Parameter(s): P033
Provides a software trip (Load Loss fault) when the current drops below this level for the time specified
in [Load Loss Time].
Values Default: 0.0 (Disabled)
Min/Max: 0.0/Drive Rated Amps
Display: 0.1 Amps
A185 [Load Loss Time] Related Parameter(s): P033
Sets the required time for the current to be below [Load Loss Level] before a Load Loss fault occurs.
Values Default: 0 Secs (Disabled)
Min/Max: 0/9999 Secs
Display: 1 Secs
A186 [Stall Fault Time]
Sets the time that the drive will remain in stall mode before a fault is issued.
Options 0 “60 Seconds” (Default)
1 “120 Seconds”
2 “240 Seconds”
3 “360 Seconds”
4 “480 Seconds”
5 “Flt Disabled”