Programming and Parameters 3-7
Basic Program Group
P031 [Motor NP Volts] Related Parameter(s): b004, A170, A171, A172, A173
Stop drive before changing this parameter.
Set to the motor nameplate rated volts.
Values Default: Based on Drive Rating
Min/Max: 20/Drive Rated Volts
Display: 1 VAC
P032 [Motor NP Hertz] Related Parameter(s): A170, A171, A172, A173, A181, A182
Stop drive before changing this parameter.
Set to the motor nameplate rated frequency.
Values Default: 60 Hz
Min/Max: 15/320 Hz
Display: 1 Hz
P033 [Motor OL Current] Related Parameter(s): P042, T055, T060, T065, A175, A179,
A180
, A181, A183
Set to the maximum allowable motor current.
The drive will fault on an F7 Motor Overload
if the value of this parameter is exceeded by 150% for 60
seconds.
Values Default: Drive Rated Amps
Min/Max: 0.0/(Drive Rated Amps × 2)
Display: 0.1 Amps
P034 [Minimum Freq] Related Parameter(s): b001, b002, P035, T070, T074,
A171
, A172, A173, d302
Sets the lowest frequency the drive will output continuously.
Values Default: 0.0 Hz
Min/Max: 0.0/320.0 Hz
Display: 0.1 Hz
P035 [Maximum Freq] Related Parameter(s): b001, b002, P034, T071, T075, T082
T083, T085, T086, A171, A172, A173, d302
Stop drive before changing this parameter.
Sets the highest frequency the drive will output.
Values Default: 60.0 Hz
Min/Max: 0.0/320.0 Hz
Display: 0.1 Hz