EasyManuals Logo

Allen-Bradley SMC-50 User Manual

Allen-Bradley SMC-50
292 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #160 background imageLoading...
Page #160 background image
160 Rockwell Automation Publication 1560F-UM001A-EN-P - June 2019
Chapter 9 Troubleshooting
V Control Loss 37 In All Modes
Loose connection at Control Terminals 1 (+L1)
and 2 (-L2)
Low line voltage condition
Check the control power and verify it is within the specification;
check the connections and grounding to the controller control
terminals.
Replace the control module.
TB Input:1, 2, 3 and 4
38, 39, 40,
and 41
In All Modes
The condition to generate the TB Input fault is
satisfied
Terminal wiring configuration or fault N.O./
N.C. configuration of input is incorrect
Clear the fault condition.
Rewire and/or reconfigure the input.
Voltage Unbalance or
Current Imbalance
42 or 18 Running
Power line unbalance is greater than the
programmed value
The delay time programmed is too short for
the application
Check the power system and correct if necessary or change the
programmed value.
Extend the delay time to match the application requirements.
Disable this fault/alarm feature.
Und Pwr Real
(1)
43 Running
Abnormally reduced real (MW) power draw
by the motor possibly due to broken
mechanical connection (belt, gears, etc.)
between motor and load
•Pump cavitation
Programmed setting is incorrect for the
application
Repair/replace the condition causing the reduced real power
load.
Modify the programmed fault/alarm parameters to better suit
the application.
Disable the fault/alarm feature.
Ovr Pwr Real
(1)
44 Running
Abnormally high real (KW) power draw by the
motor
Programmed setting is incorrect for the
application
Repair/replace the condition causing the high KW power draw.
Modify the programmed fault/alarm parameters to better suit
the application.
Disable the fault/alarm feature.
Un Pwr Reac+
(1)
45 Running
Abnormally reduced reactive (+MVAR) power
produced by the motor
Programmed setting is incorrect for the
application
Repair/replace the condition causing the reduced +MVAR power
draw.
Modify the programmed fault/alarm parameters to better suit
the application.
Disable the fault/alarm feature.
Ov Pwr Reac+
(1)
46 Running
Abnormally high reactive (+MVAR) power
produced by the motor
Programmed settings are incorrect for the
application
Repair/replace the condition causing the high +MVAR power
draw.
Modify the programmed fault/alarm parameters to better suit
the application.
Disable the fault/alarm feature.
Und Pwr App
(1)
47 Running
Abnormally reduced apparent (MVA) power
draw by the motor
Programmed settings are incorrect for the
application
Repair/replace the condition causing the reduced +MVA power
draw.
Modify the programmed fault/alarm parameters to better suit
the application.
Disable the fault/alarm feature.
Ovr Pwr App
(1)
48 Running
Abnormally high apparent (MVA) power draw
by the motor
Programmed settings are incorrect for the
application
Repair/replace the condition causing the high +MVA power
draw.
Modify the programmed fault/alarm parameters to better suit
the application.
Disable the fault/alarm feature.
Frequency 49 Running
Speed control regulation system of the
generator prime mover (for example, diesel
engine) is unable to adjust to current load
conditions or is defective
Abnormal power grid connections; power
generation source is operating outside its
normal frequency limits or range
Reduce the generator load, increase generator output, replace
the speed control system, or generator.
NOTE: For a diesel generator system, Rockwell Automation
recommends it be oversized by a factor of three for Soft Start
applications.
Contact the power company for additional information.
Modify the programmed fault/alarm parameters to better suit
the application.
PM Hours 50 In All Modes
The number of hours programmed in the PM
Hours Parameter has been reached
Perform required maintenance and reset the PM Hours
parameter.
Disable this fault/alarm feature.
PM Starts 51 Pre-Start
The number of Starts programmed in the PM
Start Parameter has been reached
Perform required maintenance and reset the PM Hours
parameter.
Disable this fault/alarm feature.
Power Quality: A, B,
or C
52, 53, or 54 Start or Stop
Incoming 3-phase voltage instability or
distortion
High impedance line or load connection
Check supply voltage for capability to start/stop the motor; check
for loose connections on the line side or motor side of the power
wires.
Verify and correct the input power quality issue
Disable this fault/alarm feature.
Table 58 - Fault Display Explanation (Continued)
Display Fault Code Fault Enabled Possible Causes Possible Solutions

Table of Contents

Other manuals for Allen-Bradley SMC-50

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Allen-Bradley SMC-50 and is the answer not in the manual?

Allen-Bradley SMC-50 Specifications

General IconGeneral
BrandAllen-Bradley
ModelSMC-50
CategoryController
LanguageEnglish

Related product manuals