EasyManuals Logo

Allen-Bradley SMC-50 User Manual

Allen-Bradley SMC-50
292 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #161 background imageLoading...
Page #161 background image
Rockwell Automation Publication 1560F-UM001A-EN-P - June 2019 161
Troubleshooting Chapter 9
Power Quality: THD V 55 Running
The current mix of loads on the power line
contributing to the THD V has exceeded the
programmed THD V level and/or time
Check the mix of loads (what was added, what was changed);
modify the load mix if necessary.
Change the programmed THD V level and/or delay time.
Disable this fault/alarm feature.
Power Quality: THD I 56 Running
The current mix of loads on the power line
contributing to the THD I has exceeded the
programmed THD I level and/or time
Check the mix of loads (what was added, what was changed);
modify the load mix if necessary.
Change the programmed THD I level and/or delay time.
Disable this fault/alarm feature.
Config Change 57 In All Modes A controller parameter has been modified Disable this fault/alarm feature.
Ground Fault X058
(2)
Running
The ground fault current level has exceeded
the programmed value
The delay time is too short for the application
NOTE: An optional 150-SM2 Ground Fault PTC
Module is required for this fault.
Check the power system and motor; correct if necessary.
Check the programmed ground fault levels to match application
requirements; modify if necessary.
Extend the delay time to match the application requirements.
Disable this fault/alarm feature.
Motor PTC X059
(2)
In All Modes
Motor ventilation is blocked.
Motor duty cycle is exceeded
PTC open or shorted
NOTE: An optional 150-SM2 Ground Fault PTC
Module is required for this fault.
Check for proper ventilation.
Check application duty cycle.
Wait for motor to cool or provide external cooling, then check
resistance of PTC.
Disable this fault/alarm feature.
SCR Overtemp or PTC
Power Pole
60 or 10 In All Modes
Controller ventilation blocked
Controller duty cycle exceeded
Ambient temperature limit exceeded
•Failed thermistor
Check for proper controller ventilation.
Check application-appropriate duty cycle.
Wait for controller to cool or provide external cooling if ambient
temperature is high.
Replace power module or control module as needed.
I/O Config 61 Pre-Start
The configuration of the control I/O does not
meet the system rules
Modify the control I/O configuration to meet the established
rules.
Test Fault 62 In All Modes
The SMC-50 control module’s Push to Reset/
Hold to Test push button was pressed for more
than three seconds, but less than ten
The SMC-50 control module’s Push to Reset/
Hold to Test push button is stuck or damaged
To reset the Test fault, press the Push to Reset/Hold to Test push
button for less than two seconds.
NOTE: Only use the Push to Reset push button when absolutely
necessary.
Attempt to dislodge the push button or replace the control
module if necessary.
Und PF Lag 63 In All Modes
A lagging PF is abnormally under the typical
value; less inductance or more capacitance
has been introduced to the power line
A programmed setting or time value is
incorrect for the application
Determine the cause of the reduced Lagging PF.
Modify the programmed fault/alarm parameters to better suit
the application.
Disable the fault/alarm feature.
Und PF Lead 64 Running
A leading PF is abnormally under the typical
value; less inductance or more capacitance
has been introduced to the power line
A programmed setting or time value is
incorrect for the application
Determine the cause of the reduced Leading PF
Modify the programmed fault/alarm parameters to better suit
the application.
Disable the fault/alarm feature.
Ovr PF Lag 65 Running
A lagging PF is abnormally over the typical
value; more inductance or less capacitance
has been introduced to the power line
A programmed setting or time value is
incorrect for the application
Determine the cause of the Over PF Lagging
Modify the programmed fault/alarm parameters to better suit
the application.
Disable the fault/alarm feature.
Ovr PF Lead 66 Running
A leading PF is abnormally under the typical
value; less inductance or more capacitance
has been introduced to the power line
A programmed setting or time value is
incorrect for the application
Determine the cause of the Over PF Leading.
Modify the programmed fault/alarm parameters to better suit
the application.
Disable the fault/alarm feature.
-MVAR Over
(1)
67 Running
Abnormally high reactive (-MVAR) power
consumed by the motor
Programmed settings are incorrect for the
application
Repair/replace the condition causing the high -MVAR.
Modify the programmed fault/alarm parameters to better suit
the application.
Disable the fault/alarm feature.
-MVAR Under
(1)
68 Running
Abnormally reduced reactive (-MVAR) power
consumed by the motor
Programmed settings are incorrect for the
application
Repair/replace the condition causing the reduced -MVAR.
Modify the programmed fault/alarm parameters to better suit
the application.
Disable the fault/alarm feature.
RTC Battery Low 69 Pre-Start
Battery reading is below the acceptable level
to potentially maintain the real time clock and
calendar
Replace battery (CR2032) as soon as possible.
Table 58 - Fault Display Explanation (Continued)
Display Fault Code Fault Enabled Possible Causes Possible Solutions

Table of Contents

Other manuals for Allen-Bradley SMC-50

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Allen-Bradley SMC-50 and is the answer not in the manual?

Allen-Bradley SMC-50 Specifications

General IconGeneral
BrandAllen-Bradley
ModelSMC-50
CategoryController
LanguageEnglish

Related product manuals