Rockwell Automation Publication 1560F-UM001A-EN-P - June 2019 159
Troubleshooting Chapter 9
Undervoltage 20 Running
Power line grid voltage is less than the
programmed value
Abnormal voltage regulation
The parameter settings and or delay time
programmed are not suited for the
application
Check the power system and correct if necessary. NOTE: If the
power source is a backup generator, check the stability of the
generator voltage regulator. Replace if necessary.
Modify the parameter and/or extend the delay time to match the
application requirements.
Disable this fault/alarm feature.
Overload 21 Running
Motor overloaded
Overload parameters are not matched to the
motor
Check motor overload condition.
Check programmed values for overload class and motor FLC;
verify current draw of the motor.
Disable this fault/alarm feature.
(3)
Underload 22 Running
Broken motor shaft, belt, grating, etc.
•Pump cavitation
Programmed setting incorrect for application
Check machine drive components and loading.
Check pump system.
Repair or replace motor.
Check programmed settings.
Disable this fault/alarm feature.
Jam 23 Running
Motor current has exceeded the user
programmed jam level for the programmed
time
Correct source of jam or excessive loading.
Check programmed time value.
Disable this fault/alarm feature.
Stall 24 Running
The motor did not reach full speed by the end
of the programmed ramp time
Incorrect programmed setting
Check pump system, machine drive components, and loading;
repair or replace motor, if necessary.
Check programmed settings.
Disable this fault/alarm feature.
Phase Reversal 25 Prestart Only
The controller is not detecting incoming
supply voltage in the expected ABC sequence
Check power wiring and correct, if necessary.
Disable this fault/alarm feature.
Exp Removed x026
(2)
In All Modes
Expansion module is loose or removed
Expansion module is defective
Reseat or replace the expansion module connector to the control
module and tighten module screws.
Replace defective module.
Exp Incompat x027
(2)
In All Modes
Expansion module is inserted into an
incompatible control module port number
Controller firmware is not compatible with
the expansion module
Expansion module is defective
Insert the expansion module into a compatible control module
port.
Update the control module firmware
Replace defective module.
Expansion x028
(2)
In All Modes
Expansion module is loose or removed
Expansion module is defective
Expansion module is inserted into an
incompatible control module port number
Controller firmware is not compatible with
the expansion module
Reseat and/or replace loose/removed module and tighten
module screws.
Replace defective expansion module.
Update control module firmware.
Starts per Hour 29 Starting
The number of starts within the last hour has
exceeded the programmed value
Programmed setting is incorrect for the
application
Wait for the hour to expire, then restart the motor.
Reduce the actual number of starts per hour or increase the
programmed start time (if allowed by the application) and
controller thermal limits.
Turn off this fault/alarm feature.
CT Loss: A, B, or C 30, 31, or 32 In All Modes
Loose CT cable connection between the power
section and the control module
Phase A (F30), B (F31), or C (F32) current
transformer feedback circuit has failed
Option Module 150-SM2 with external CT
operation (Fault Code 7030, 8030)
Remove the control module from the power section; verify
connectors TB2 (A), TB3 (B), and TB4 (C) are firmly seated to the
control module.
Replace the control module and/or the power section.
Inspect the CT sensor cables for loose connections; check CTs for
damage; repair/replace CTs if necessary; replace 150-SM2 option
module if necessary.
Hall ID 33 In All Modes
Loose cables between the controller and
power section.
Incompatible power section installed with the
controller
Remove the control module from the power section; verify
connectors TB2 (A), TB3 (B), and TB4 (C) are firmly seated to the
control module.
Check the power section and replace, if necessary.
NVS Error 34 In All Modes
Controller memory corrupted
•Option module error (Fault Code 7034, 8034,
or 9034)
Modify a parameter or load parameter defaults (preferred) and
reload the customer-specific parameters.
Check the option module sensor cables.
Replace the option module.
Future Use 35 NA NA NA
V24 Loss 36 In All Modes
Loose connection at Control Terminals 1 (+L1)
and 2 (-L2)
Excessive load on internal 24V supply
Low line voltage condition
Check the control power and verify it is within the specification;
check the line connections and grounding to the SMC-50
controller control terminals.
Replace the control module.
Table 58 - Fault Display Explanation (Continued)
Display Fault Code Fault Enabled Possible Causes Possible Solutions