226 Rockwell Automation Publication 1560F-UM001A-EN-P - June 2019
Appendix A Parameter Information
298 -MVAR Ov F Dly Secs 0.1/99 0.1 Enables the user to enter a time value for the Generated
Reactive Power Over Fault Delay (-MVAR Ov F Dly). If the current
actual value for the Generated Reactive Power is more than the
-MVAR Ov F Lvl for a time period greater than that defined by -
MVAR Ov F Dly, a -MVAR Ov fault will be signaled.
R/W
299 -MVAR Ov A Lvl MVAR -1000/0 0.000 Enables the user to enter a value for the Generated Reactive
Power Over Alarm Level (-MVAR Ov A Lvl). If the current actual
value for Generated Reactive Power is more than the -MVAR Ov
A Lvl for a period greater than that defined by -MVAR Ov A Dly, a
-MVAR Ov Alarm will be signaled.
R/W
300 -MVAR Ov A Dly Secs 0.1/99 0.1 Enables the user to enter a time value for the Generated
Reactive Power Over Alarm Delay (-MVAR Ov A Dly). If the
current actual value for the Generated Reactive Power is more
than the -MVAR Ov A Lvl for a period greater than that defined
by -MVAR Ov A Dly, a -MVAR Ov alarm will be signaled.
R/W
301 -MVAR Un F Lvl MVAR -1000/0 0.000 Enables the user to enter a value for the Generated Reactive
Power Under Fault Level (-MVAR Un F Lvl). If the current actual
value for Generated Reactive Power is less than the -MVAR Un F
Lvl for a period greater than that defined by -MVAR Un F Dly, a -
MVAR Un Fault will be signaled.
R/W
302 -MVAR Un F Dly Secs 0.1/99 0.1 Enables the user to enter a time value for the Generated
Reactive Power Under Fault Delay (-MVAR Un F Dly). If the
current actual value for Generated Reactive Power is less than
the -MVAR Un F Lvl for a period greater than that defined by -
MVAR Un F Dly, a -MVAR Un Fault will be signaled.
R/W
303 -MVAR Un A Lvl MVAR -1000/0 0.000 Enables the user to enter a value for the Generated Reactive
Power Under Alarm Level (-MVAR Un A Lvl). If the current actual
value for Generated Reactive Power is less than the -MVAR Un A
Lvl for a period greater than that defined by -MVAR Un A Dly, a
MVAR Un Alarm will be signaled.
R/W
304 -MVAR Un A Dly Secs 0.1/99 0.1 Enables the user to enter a time value for the Generated
Reactive Power Under Alarm Delay (-MVAR Un A Dly). If the
current actual value for Generated Reactive Power is less than
the -MVAR Un A Lvl for a period greater than that defined by -
MVAR Un A Dly, a -MVAR Un Alarm will be signaled.
R/W
305 Starting Torque % 0/300 100 Enables the user to enter Starting Torque value required for a
torque start operation.
R/W
306 Starting Torque 2 % 0/300 100 Enables the user to enter an alternate Starting Torque required
for a torque start operation.
R/W
Table 66 - SMC -50 Parameter List (Continued)
Number Name Unit Min/Max Default Enum Text Description R/W