Rockwell Automation Publication 1560F-UM001A-EN-P - June 2019 233
Parameter Information Appendix A
SM2.16
(GF)
Phase Shift A Deg -12.5/12.5 0 Displayed result of the SMC-50 tuning feature determination of
the phase shift between external CT and the internal current
measuring circuitry.
R
SM2.17
(GF)
Phase Shift B Deg -12.5/12.5 0 Displayed result of the SMC-50 tuning feature determination of
the phase shift between external CT and the internal current
measuring circuitry.
R
SM2.18
(GF)
Phase Shift C Deg -12.5/12.5 0 Displayed result of the SMC-50 tuning feature determination of
the phase shift between external CT and the internal current
measuring circuitry.
R
SM2.19
(GF)
Parameter Mgmt 0/1 0 [Ready]
Factory Default
Ready: Waiting for command to set defaults.
Factory Default:
Set all writable parameters to factory default
values.
R/W
Table 67 - 150-SM2 Option Card Parameters (Continued)
Number Name Unit Min/Max Default Enum Text Description Read/
Write